background image

Page 18

506083−01 03/08

Table 4. HFC−410A Normal Operating Pressures (10 and S5 psig)

IMPORTANT

Use this table to perform maintenance checks; it is not a procedure for
charging the system. Minor variations in these pressures may be due to
differences in installations. Significant deviations could mean that the system
is not properly charged or that a problem exists with some component in the
system.

TSA*H4

 

−036

−042

−048

−060

5

F (

5

C)*

Liquid / Suction

Liquid / Suction

Liquid / Suction

Liquid / Suction

Expansion Valve (TXV)

65 (18)

238 / 132

236 / 138

238 / 136

239 / 133

70 (21)

254 / 135

253 / 140

256 / 138

258 / 135

75 (24)

273 / 138

273 / 141

277 / 139

278 / 136

80 (27)

293 / 140

296 / 142

299 / 140

300 / 137

85 (29)

316 / 142

318 / 143

320 / 139

323 / 138

90 (32)

340 / 143

341 / 144

343 / 140

346 / 139

95 (35)

366 / 144

366 / 146

369 / 141

370 / 140

100 (38)

392 / 145

392 / 147

395 / 142

396 / 142

105 (41)

420 / 147

417 / 148

422 / 144

415 / 143

110 (43)

449 / 148

445 / 149

450 / 146

449 / 145

115 (45)

480 / 149

475 / 151

481 / 148

476 / 147

Table 5. HFC−410A Temperature (°F) − Pressure (Psig)

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

°F

Psig

32

100.8

48

137.1

63

178.5

79

231.6

94

290.8

110

365.0

125

445.9

141

545.6

33

102.9

49

139.6

64

181.6

80

235.3

95

295.1

111

370.0

126

451.8

142

552.3

34

105.0

50

142.2

65

184.3

81

239.0

96

299.4

112

375.1

127

457.6

143

559.1

35

107.1

51

144.8

66

187.7

82

242.7

97

303.8

113

380.2

128

463.5

144

565.9

36

109.2

52

147.4

67

190.9

83

246.5

98

308.2

114

385.4

129

469.5

145

572.8

37

111.4

53

150.1

68

194.1

84

250.3

99

312.7

115

390.7

130

475.6

146

579.8

38

113.6

54

152.8

69

197.3

85

254.1

100

317.2

116

396.0

131

481.6

147

586.8

39

115.8

55

155.5

70

200.6

86

258.0

101

321.8

117

401.3

132

487.8

148

593.8

40

118.0

56

158.2

71

203.9

87

262.0

102

326.4

118

406.7

133

494.0

149

601.0

41

120.3

57

161.0

72

207.2

88

266.0

103

331.0

119

412.2

134

500.2

150

608.1

42

122.6

58

163.9

73

210.6

89

270.0

104

335.7

120

417.7

135

506.5

151

615.4

43

125.0

59

166.7

74

214.0

90

274.1

105

340.5

121

423.2

136

512.9

152

622.7

44

127.3

60

169.6

75

217.4

91

278.2

106

345.3

122

428.8

137

519.3

153

630.1

45

129.7

61

172.6

76

220.9

92

282.3

107

350.1

123

434.5

138

525.8

154

637.5

46

132.2

62

175.4

77

224.4

93

286.5

108

355.0

124

440.2

139

532.4

155

645.0

47

134.6

78

228.0

109

360.0

140

539.0

INSTALLING SERVICE VALVE CAPS

Disconnect gauge set and install all service valve caps for
both the liquid and suction line valves.

INSTALL CAPS

OUTDOOR UNIT

SERVICE VALVES

Figure 32. Installing Service Valve Caps

System Operation

The outdoor unit and indoor blower will cycle on and off as
dictated by demands from the room thermostat. When the
thermostat’s blower switch is in the 

ON

 position, the indoor

blower will operate continuously.

HIGH PRESSURE SWITCH

TSA*H4 units are equipped with a high-pressure switch
that is located in the liquid line of the compressor. The
switch (SPST, manual reset, normally closed) removes
power from the compressor when discharge pressure
rises above factory setting at 590 + 10 psi.

Содержание TSA036H4N41

Страница 1: ...41 TSA048H4N41 and TSA060H4N41 AIR CONDITIONER 506083 01 03 08 Table of Contents Shipping and Packing List 1 TSA H4 Air Conditioners 1 Unit Dimensions 2 General Information 2 Recovering Refrigerant fr...

Страница 2: ...ble 1 shows torque values for fasteners Table 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 in lb 2 NM Machine screws 10 28 in lb 3 NM Compressor...

Страница 3: ...nd use an appropriately sized wrench to turn an additional 1 6 turn clockwise as illustrated in figure 2 To Open and Close Angle Type Service Valve A valve stem cap protects the valve stem from contam...

Страница 4: ...as follows With Torque Wrench Finger tighten and then tighten per table 1 Without Torque Wrench Finger tighten and use an appropriately sized wrench to turn an additional 1 12 turn clockwise as illus...

Страница 5: ...CONSIDERATIONS Consider the following when positioning the unit Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the install...

Страница 6: ...ne that ran from condenser to evaporator coil Refrigerant was metered into the evaporator by utilizing temperature pressure evaporation effects on refrigerant in the small RFC line The length and bore...

Страница 7: ...caps or service valve stub caps until you are ready to make connections WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in the low side shell and suction tubi...

Страница 8: ...nnect manifold gauge set from service ports cool down piping with wet rag and remove all wrappings Do not reinstall cores until after evacuation procedure Reinstall service caps if desired to close of...

Страница 9: ...ushing Existing System IMPORTANT The line set and indoor unit coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushin...

Страница 10: ...gerant to flow into the system through the suction line valve Allow the refrigerant to pass from the cylinder and through the line set and the indoor unit coil before it enters the recovery machine 4...

Страница 11: ...aining Teflon washer around the other end of the TXV Lightly lubricate connector threads and expose surface of the Teflon ring with refrigerant oil 5 Attach the liquid line assembly to the TXV Finger...

Страница 12: ...or unit 6 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be detected NOTE Amounts of refrigerant will vary with line lengths 7 Check all joints for leak...

Страница 13: ...to break the vacuum and install a new filter drier in the system 4 Evacuate the system again Then weigh the appropriate amount of HFC 410A refrigerant as listed on unit nameplate into the system 5 Mo...

Страница 14: ...e only with copper conductors NOTE A complete unit wiring diagram is located inside the unit control box cover NOTE See unit wiring diagram for power supply connections If indoor unit is not equipped...

Страница 15: ...ine service port INDOOR COIL AIRFLOW CHECK Check indoor coil airflow using the Delta T DT process as illustration in figure 27 DETERMINING CHARGE METHOD To determine the correct charging method use th...

Страница 16: ...utdoor ambient temperature 64 F and BELOW 1 Check Liquid and suction line pressures 2 Compare unit pressures with Table 27 Normal Operating Pressures 3 Conduct leak check evacuate as previously outlin...

Страница 17: ...erant If refrigerant is added or removed verify charge using the Approach Method 64 F and BELOW 65 F and ABOVE ABOVE or BELOW F C 036 042 048 060 65 18 13 7 2 10 5 6 8 4 4 8 4 4 75 24 9 5 0 7 3 9 8 4...

Страница 18: ...7 190 9 83 246 5 98 308 2 114 385 4 129 469 5 145 572 8 37 111 4 53 150 1 68 194 1 84 250 3 99 312 7 115 390 7 130 475 6 146 579 8 38 113 6 54 152 8 69 197 3 85 254 1 100 317 2 116 396 0 131 481 6 147...

Страница 19: ...ineering Handbook for optional accessories that may apply to this unit The following may or may not apply Timed Off Control Sound Cover Suction Line Drier Stand Off Kit Low Ambient Kit Homeowner Infor...

Страница 20: ...vides temporary heat supplied by the auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperatu...

Отзывы: