XP-6514 4/09
9
Section 1 Installation
Section 1 Installation
1.1 General
Have a Lennox dealer install the generator set outdoors
according to the instructions in this manual. Do not
install this generator set indoors.
Use the specifications provided here only in the initial
planning. Use the generator set and transfer switch
dimension drawings and wiring diagrams for installation.
1.2 Lifting
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
WARNING
Model
Weight, kg (lb.)
RGEN12
186 (410)
RGEN17/18
227 (500)
Figure 1-1
Approximate Weights
Approximate generator set weights are shown in
Figure 1-1. Use lifting bars inserted through the holes in
the skid to lift the unit. See Figure 1-2 or Figure 1-4 for
lifting hole locations.
1.3 Generator Set Inspection
Complete a thorough inspection of the generator set.
Check for the following:
1. Inspect the generator set for loose or damaged
parts or wires. Repair or tighten any loose parts
before installation.
2. Check the engine oil. Fill, if necessary, with the
recommended viscosity and grade of oil.
Use
synthetic oil, API (American Petroleum Institute)
Service Class SG or higher.
See XP-6515,
Operation Manual, for additional information.
1.4 Location and Mounting
See Figure 1-2 or Figure 1-4 for the generator set
dimensions and fuel and electric inlet locations. The
drawing dimensions are shown in millimeters, with
inches in brackets.
Install the generator set outdoors. Provide the minimum
clearance around the generator set shown in Figure 1-3
or Figure 1-5. Locate the generator set so that the hot
exhaust does not blow on plants or other combustible
materials.
Do not install the generator set where
exhaust gas could accumulate and seep inside or be
drawn into a potentially occupied building.
The generator set is shipped on a plastic mounting pad.
Prepare a flat, level mounting area covered with a weed
barrier and gravel as shown in Figure 1-3 or Figure 1-5.
Set the plastic mounting pad directly on the gravel. Do
not install the mounting pad directly on grass.
Содержание RGEN12
Страница 11: ...XP 6514 4 09 11 Section 1 Installation Figure 1 3 Generator Set Clearances RGEN12 ADV 7466B...
Страница 13: ...XP 6514 4 09 13 Section 1 Installation Figure 1 5 Generator Set Clearances RGEN17 18 ADV 7341B B...