Safety Precautions and Instructions

Battery gases. Explosion can cause
severe injury or death.

Battery gases

can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging.

Do not dispose of a

battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from

your

body

before

touching

batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.

Ventilate the

compartments containing batteries to
prevent accumulation of explosive
gases.

Battery short circuits.

Explosion

can cause severe injury or death.

Short circuits can cause bodily injury
and/or

equipment

damage.

Disconnect

the

battery

before

generator

set

installation

or

maintenance.

Remove all jewelry

before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting

the

battery.

Never

connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery

condition

by

shorting the

terminals together.

Engine Backfire/Flash
Fire

Fire.
Can cause severe injury or death.

Do not smoke or permit flames or
sparks near fuels or the fuel system.

WARNING

Servicing the air cleaner. A sudden
backfire can cause severe injury or
death.

Do not operate the generator

set with the air cleaner removed.

Servicing the fuel system. A flash
fire can cause severe injury or death.

Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when

removing

the

fuel

line

or

carburetor.

Combustible materials. A fire can
cause

severe

injury

or

death.

Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BC

for

electrical

fires

or

as

recommended by the local fire code or
an authorized agency.

Train all

personnel

on

fire

extinguisher

operation

and

fire

prevention

procedures.

Exhaust System

Carbon monoxide.
Can

cause

severe

nausea,

fainting, or death.

The

exhaust

system

must

be

leakproof and routinely inspected.

WARNING

Generator set operation.

Carbon

monoxide can cause severe nausea,
fainting, or death.

Carbon monoxide

is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a potentially
occupied building through windows, air
intake vents, or other openings.

Carbon

monoxide

symptoms.

Carbon monoxide can cause severe
nausea, fainting, or death.

Carbon

monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,

colorless,

tasteless,

nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:

D

Light-headedness, dizziness

D

Physical fatigue, weakness in
joints and muscles

D

Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision

D

Stomachache, vomiting, nausea

If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.

Alert others to the

possibility

of

carbon

monoxide

poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.

Fuel System

Explosive fuel vapors.
Can cause severe injury or death.

Use extreme care when handling,
storing, and using fuels.

WARNING

Gas fuel leaks.

Explosive fuel

vapors can cause severe injury or
death.

Fuel leakage can cause an

explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ounces

per

square

inch

(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.

Содержание RGEN12

Страница 1: ...follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury Read and follow the Safety Precautions and Instructions section 506087 01 INSTALLATION INST...

Страница 2: ...d the product identification numbers from the generator set nameplate s Model Designation Specification Number Serial Number Accessory Number Accessory Description Engine Identification Record the pro...

Страница 3: ...r set or connected equipment disable the generator set as follows 1 Move the generator set master switch to the OFF position 2 Disconnect the power to the battery charger 3 Remove the battery cables n...

Страница 4: ...isk of fire or explosion Equip the compartment or nearby area with a fully charged fire extinguisher Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire...

Страница 5: ...nd because these conditions increase the risk of electrocution Welding on the generator set Can cause severe electrical equipment damage Before welding on the generator set perform the following steps...

Страница 6: ...extremely hot during operation Servicing the engine heater Hot parts can cause minor personal injury or property damage Install the heater before connecting it to power Operatingtheheater beforeinsta...

Страница 7: ...0 Field connection terminal block location 11 Spark plug locations both sides 12 Oil drain hose 13 Oil drain valve 14 Oil filter 15 Exhaust 16 Equipment ground 17 Battery charger 18 DSAI lead location...

Страница 8: ...tery location battery purchased separately 14 Oil drain hose 15 Nameplate location on base 16 Oil drain valve 17 Exhaust 18 Carburetor heater access opening 19 LP fuel orifice location inside hose fit...

Страница 9: ...wing 1 Inspect the generator set for loose or damaged parts or wires Repair or tighten any loose parts before installation 2 Check the engine oil Fill if necessary with the recommended viscosity and g...

Страница 10: ...XP 6514 4 09 10 Section 1 Installation Figure 1 2 Generator Set Mounting Details and Dimensions RGEN12 ADV 7466A...

Страница 11: ...XP 6514 4 09 11 Section 1 Installation Figure 1 3 Generator Set Clearances RGEN12 ADV 7466B...

Страница 12: ...XP 6514 4 09 12 Section 1 Installation Figure 1 4 Generator Set Mounting Details and Dimensions RGEN17 18 ADV 7341A B...

Страница 13: ...XP 6514 4 09 13 Section 1 Installation Figure 1 5 Generator Set Clearances RGEN17 18 ADV 7341B B...

Страница 14: ...ated kW m3 min cfm RGEN12 3 8 135 RGEN17 18 5 3 187 Exhaust gas exiting the enclosure at rated kW _C _F 216 420 Figure 1 6 Exhaust Flow and Temperature 1 4 2 Air Requirements The generator set require...

Страница 15: ...ces See Figure 1 11 or Figure 1 12 for fuel consumption Contact the fuel supplier for flow rate information or a gas meter upgrade Figure 1 2 or Figure 1 4 shows the location of the fuel inlet connect...

Страница 16: ...e field while maintaining emissions standard compliance A trained technician or a Lennox dealer can convert the fuel system Accidental starting Can cause severe injury or death Disconnect the battery...

Страница 17: ...osition 2 Disconnect the power to the battery charger 3 Disconnect the generator set engine starting battery negative lead first 4 Turn off the fuel supply 5 Remove the hose clamp and fuel hose from t...

Страница 18: ...ng to the natural gas port and plugging the LP port For the RGEN12 model disconnect the DSAI leads for LP vapor See Figure 1 17 and Figure 1 18 1 7 2 Fuel Conversion RGEN17 18 For LP vapor fuel an ori...

Страница 19: ...nerator set To convert from LP vapor to natural gas remove the fuel orifice and connect the DSAI leads together 1 8 Electrical Connections Hazardous voltage Backfeed to the utility system can cause pr...

Страница 20: ...ect to a circuit that is supplied by the generator set if utility power is lost See Section 1 5 for more information about the 120 VAC power requirement 1 8 2 Remote Start Connection Connect leads 3 a...

Страница 21: ...avoid touching the battery terminals with tools or other metal objects Remove all jewelry before servicing the equipment Discharge static electricity from your body before touching batteries by first...

Страница 22: ...the possibility of electrical interference Verify that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas Verify that the electrical installat...

Страница 23: ...retor Heater Location on Engine bulkhead removed to show heater location The heater thermostat is installed in the cord Figure 1 29 shows the location of the thermostat on the power cord Note Do not p...

Страница 24: ...r model is set at the factory and should not normally require changes The controller s configuration mode allows adjustment of the system parameters listed in this section Use the instructions in this...

Страница 25: ...ontroller to power down after 48 hours of inactivity The generator set master switch must be in AUTO for the sleep mode to function The default setting for controllers with application code version 1...

Страница 26: ...ntroller display changes when the up or down arrow key is pressed X in the runtime hours display above denotes any number from 0 to 9 Press the down arrow key and then the up arrow key 3 times to ente...

Страница 27: ...r set shuts down The generator set continues to run with the new settings until it shuts down but then reverts to the previous settings at the next startup if the changes have not been saved 1 14 1 Vo...

Страница 28: ...s in Figure 1 34 through Figure 1 36 during the following procedure 1 Attach a frequency meter to the AC output leads or an electrical outlet on the load side of the generator set 2 Start and run the...

Страница 29: ...o raise or lower the voltage stability gain in smaller increments Parameter 2P To enter volts Hz adjustment mode Parameter 3P To raise or lower the volts Hz 00 low 09 high or Hold Wait about 5 seconds...

Страница 30: ...ility gain fine adjustment mode Parameter 5P To raise or lower the engine governor stability gain in smaller increments 4 P 4 P or or or Continued from Figure 1 34 Press 5 P 5 P Shaded boxes show whic...

Страница 31: ...are 3 options when the display says SAVE Press or To return to the first parameter coarse voltage adjustment to check or change settings before saving See Figure 1 34 Yes or no flashes when the up or...

Страница 32: ...diagram numbers and locations Wiring Diagram Description Drawing Number Page Schematic Diagram RGEN12 ADV 7592 33 Point to Point Wiring Diagram RGEN12 GM62285 34 Schematic Diagram RGEN17 18 ADV 7353...

Страница 33: ...XP 6514 4 09 33 Section 2 Wiring Diagrams Figure 2 2 Schematic Diagram Single Phase RGEN12 ADV 7592...

Страница 34: ...XP 6514 4 09 34 Section 2 Wiring Diagrams Figure 2 3 Point to Point Wiring Diagram Single Phase RGEN12 GM62285...

Страница 35: ...XP 6514 4 09 35 Section 2 Wiring Diagrams Figure 2 4 Schematic Diagram Single Phase RGEN17 18 ADV 7353 F...

Страница 36: ...XP 6514 4 09 36 Section 2 Wiring Diagrams Figure 2 5 Point to Point Wiring Diagram Single Phase RGEN17 18 GM52541 E...

Отзывы: