Section 1 Installation

1.11 Prestart Installation Check

Review the entire installation section. Inspect all wiring
and connections to verify that the generator set is ready
for operation. Check all items in the following Prestart
Checklist.

Prestart Checklist

Air Cleaner.

Check that a clean air cleaner element is

installed to prevent unfiltered air from entering the
engine. See the generator set operation manual for
instructions.

Air Inlets.

Check for clean and unobstructed air inlets.

Battery.

Check for tight battery connections. Consult

the

battery manufacturer’s

instructions regarding

battery care and maintenance.

Exhaust System.

Check for exhaust leaks and

blockages. Check the muffler condition.

D

Inspect the exhaust system components for cracks,

leaks, and corrosion. Check for tight exhaust system
connections.

D

Check for corroded or broken metal parts and replace

them as needed.

D

Check that the exhaust outlet is unobstructed.

Oil Level.

Maintain the oil level at or near, not over, the

full mark on the dipstick.

Operating Area.

Check for obstructions that could

block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.

1.12 Startup Notification

Complete

the

startup and

installation checklists

supplied with the startup notification form. Complete
and sign the startup notification form and submit copies
as instructed on the form.

Standby systems not registered within 60 days of
startup

are

automatically

registered

using

the

manufacturer’s ship date as the startup date.

1.13 Controller Configuration

1.13.1 System Parameters

The controller configuration for each generator model is
set at the factory and should not normally require
changes. The controller’s configuration mode allows
adjustment of the system parameters listed in this
section. Use the instructions in this section to check the
configuration after installation and change them to
match the settings shown in Figure 1-30, if necessary.

Parameter

Setting

Definition

Unit’s system
voltage and
frequency

Uu01

Single phase, 120/240 VAC

Engine type

Ec00

RGEN12

Ec12

RGEN17/18

Communication
setting *

Cn00

No J1939 communication.
Sleep mode enabled
(48-hour power down in
AUTO).

Cn01

[

J1939 communication
enabled. Sleep mode
disabled (no power down in
AUTO).

* Controller application code version 1.13 or higher.

[

Default setting for application code version 1.13 or higher.

Figure 1-30

Controller Configuration Parameters

The controller will automatically exit the configuration
mode without saving any changes after about 1 minute
if no buttons are pressed.

Start the configuration

procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.

Follow the instructions in Figure 1-31 to enter the
configuration mode while the engine is not running and
then step through the following parameters. Use the up
(

) and down (

) arrow buttons to select the appropriate

setting for the application.

Note:

Be sure to save your settings before exiting the
configuration mode. The controller reverts to the
last saved settings when the master switch is
moved to the OFF/RESET position.

Voltage/frequency setting (Uu).

Select the system

voltage and frequency from the table in Figure 1-30.

Note:

The Uu parameter sets the system’s rated
voltage and frequency.

To adjust the output

(measured) voltage and frequency, see Section
1.14, Voltage and Frequency Adjustments.

Engine configuration (Ec).

The engine configuration

must match the generator set engine type.

Содержание RGEN12

Страница 1: ...follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury Read and follow the Safety Precautions and Instructions section 506087 01 INSTALLATION INST...

Страница 2: ...d the product identification numbers from the generator set nameplate s Model Designation Specification Number Serial Number Accessory Number Accessory Description Engine Identification Record the pro...

Страница 3: ...r set or connected equipment disable the generator set as follows 1 Move the generator set master switch to the OFF position 2 Disconnect the power to the battery charger 3 Remove the battery cables n...

Страница 4: ...isk of fire or explosion Equip the compartment or nearby area with a fully charged fire extinguisher Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire...

Страница 5: ...nd because these conditions increase the risk of electrocution Welding on the generator set Can cause severe electrical equipment damage Before welding on the generator set perform the following steps...

Страница 6: ...extremely hot during operation Servicing the engine heater Hot parts can cause minor personal injury or property damage Install the heater before connecting it to power Operatingtheheater beforeinsta...

Страница 7: ...0 Field connection terminal block location 11 Spark plug locations both sides 12 Oil drain hose 13 Oil drain valve 14 Oil filter 15 Exhaust 16 Equipment ground 17 Battery charger 18 DSAI lead location...

Страница 8: ...tery location battery purchased separately 14 Oil drain hose 15 Nameplate location on base 16 Oil drain valve 17 Exhaust 18 Carburetor heater access opening 19 LP fuel orifice location inside hose fit...

Страница 9: ...wing 1 Inspect the generator set for loose or damaged parts or wires Repair or tighten any loose parts before installation 2 Check the engine oil Fill if necessary with the recommended viscosity and g...

Страница 10: ...XP 6514 4 09 10 Section 1 Installation Figure 1 2 Generator Set Mounting Details and Dimensions RGEN12 ADV 7466A...

Страница 11: ...XP 6514 4 09 11 Section 1 Installation Figure 1 3 Generator Set Clearances RGEN12 ADV 7466B...

Страница 12: ...XP 6514 4 09 12 Section 1 Installation Figure 1 4 Generator Set Mounting Details and Dimensions RGEN17 18 ADV 7341A B...

Страница 13: ...XP 6514 4 09 13 Section 1 Installation Figure 1 5 Generator Set Clearances RGEN17 18 ADV 7341B B...

Страница 14: ...ated kW m3 min cfm RGEN12 3 8 135 RGEN17 18 5 3 187 Exhaust gas exiting the enclosure at rated kW _C _F 216 420 Figure 1 6 Exhaust Flow and Temperature 1 4 2 Air Requirements The generator set require...

Страница 15: ...ces See Figure 1 11 or Figure 1 12 for fuel consumption Contact the fuel supplier for flow rate information or a gas meter upgrade Figure 1 2 or Figure 1 4 shows the location of the fuel inlet connect...

Страница 16: ...e field while maintaining emissions standard compliance A trained technician or a Lennox dealer can convert the fuel system Accidental starting Can cause severe injury or death Disconnect the battery...

Страница 17: ...osition 2 Disconnect the power to the battery charger 3 Disconnect the generator set engine starting battery negative lead first 4 Turn off the fuel supply 5 Remove the hose clamp and fuel hose from t...

Страница 18: ...ng to the natural gas port and plugging the LP port For the RGEN12 model disconnect the DSAI leads for LP vapor See Figure 1 17 and Figure 1 18 1 7 2 Fuel Conversion RGEN17 18 For LP vapor fuel an ori...

Страница 19: ...nerator set To convert from LP vapor to natural gas remove the fuel orifice and connect the DSAI leads together 1 8 Electrical Connections Hazardous voltage Backfeed to the utility system can cause pr...

Страница 20: ...ect to a circuit that is supplied by the generator set if utility power is lost See Section 1 5 for more information about the 120 VAC power requirement 1 8 2 Remote Start Connection Connect leads 3 a...

Страница 21: ...avoid touching the battery terminals with tools or other metal objects Remove all jewelry before servicing the equipment Discharge static electricity from your body before touching batteries by first...

Страница 22: ...the possibility of electrical interference Verify that the leads and conduit do not interfere with the operation of the generator set or obstruct the service areas Verify that the electrical installat...

Страница 23: ...retor Heater Location on Engine bulkhead removed to show heater location The heater thermostat is installed in the cord Figure 1 29 shows the location of the thermostat on the power cord Note Do not p...

Страница 24: ...r model is set at the factory and should not normally require changes The controller s configuration mode allows adjustment of the system parameters listed in this section Use the instructions in this...

Страница 25: ...ontroller to power down after 48 hours of inactivity The generator set master switch must be in AUTO for the sleep mode to function The default setting for controllers with application code version 1...

Страница 26: ...ntroller display changes when the up or down arrow key is pressed X in the runtime hours display above denotes any number from 0 to 9 Press the down arrow key and then the up arrow key 3 times to ente...

Страница 27: ...r set shuts down The generator set continues to run with the new settings until it shuts down but then reverts to the previous settings at the next startup if the changes have not been saved 1 14 1 Vo...

Страница 28: ...s in Figure 1 34 through Figure 1 36 during the following procedure 1 Attach a frequency meter to the AC output leads or an electrical outlet on the load side of the generator set 2 Start and run the...

Страница 29: ...o raise or lower the voltage stability gain in smaller increments Parameter 2P To enter volts Hz adjustment mode Parameter 3P To raise or lower the volts Hz 00 low 09 high or Hold Wait about 5 seconds...

Страница 30: ...ility gain fine adjustment mode Parameter 5P To raise or lower the engine governor stability gain in smaller increments 4 P 4 P or or or Continued from Figure 1 34 Press 5 P 5 P Shaded boxes show whic...

Страница 31: ...are 3 options when the display says SAVE Press or To return to the first parameter coarse voltage adjustment to check or change settings before saving See Figure 1 34 Yes or no flashes when the up or...

Страница 32: ...diagram numbers and locations Wiring Diagram Description Drawing Number Page Schematic Diagram RGEN12 ADV 7592 33 Point to Point Wiring Diagram RGEN12 GM62285 34 Schematic Diagram RGEN17 18 ADV 7353...

Страница 33: ...XP 6514 4 09 33 Section 2 Wiring Diagrams Figure 2 2 Schematic Diagram Single Phase RGEN12 ADV 7592...

Страница 34: ...XP 6514 4 09 34 Section 2 Wiring Diagrams Figure 2 3 Point to Point Wiring Diagram Single Phase RGEN12 GM62285...

Страница 35: ...XP 6514 4 09 35 Section 2 Wiring Diagrams Figure 2 4 Schematic Diagram Single Phase RGEN17 18 ADV 7353 F...

Страница 36: ...XP 6514 4 09 36 Section 2 Wiring Diagrams Figure 2 5 Point to Point Wiring Diagram Single Phase RGEN17 18 GM52541 E...

Отзывы: