Section 1 Installation
Communication/Sleep Mode Setting (Cn).
(Available
on controllers with application code version 1.13 or
higher.) The communication setting enables or disables
J1939 communication, and also disables or enables the
sleep mode. When J1939 communication is enabled,
the sleep mode is turned off to allow uninterrupted
communication with a personal computer running
remote monitoring software. If remote monitoring is not
used, the communication can be turned off, enabling the
sleep mode which causes the controller to power down
after 48 hours of inactivity. The generator set master
switch must be in AUTO for the sleep mode to function.
The default setting for controllers with application code
version 1.13 or higher is Cn01, communication on/sleep
mode off.
Controllers with earlier application code
versions have communication disabled and the sleep
mode enabled. The Cn setting is not adjustable on
these earlier versions.
1.13.2 Application Code Version
To check the application code version number, HOLD
the select button while moving the generator set master
switch to RUN. (The engine will not start when the select
button is held.) Wait about 5 seconds for the application
code version number to appear on the display. See
Figure 1-31.
Содержание RGEN12
Страница 11: ...XP 6514 4 09 11 Section 1 Installation Figure 1 3 Generator Set Clearances RGEN12 ADV 7466B...
Страница 13: ...XP 6514 4 09 13 Section 1 Installation Figure 1 5 Generator Set Clearances RGEN17 18 ADV 7341B B...
Страница 33: ...XP 6514 4 09 33 Section 2 Wiring Diagrams Figure 2 2 Schematic Diagram Single Phase RGEN12 ADV 7592...
Страница 34: ...XP 6514 4 09 34 Section 2 Wiring Diagrams Figure 2 3 Point to Point Wiring Diagram Single Phase RGEN12 GM62285...
Страница 35: ...XP 6514 4 09 35 Section 2 Wiring Diagrams Figure 2 4 Schematic Diagram Single Phase RGEN17 18 ADV 7353 F...