Table 63. M3 Control Parameters
Control Parameter
Description
Units
Control Value
No
Description
Units
Max.
Default
Min.
Parameter Short
Description
Screen Name
Block 5 Miscellaneous Parameters
112
HEAT STAGING
OPTION
Heating Staging Option
0
2
2
Option
Heating staging options:
0-
No heating operation.
1-
Discharge air control with
up to four stages.
2-
Thermostat operation.
113
EN RET AIR TMP LMT
Enable Return Air
Temperature Limit
0
0
1
Option
Enables return air temperat
ure limit option.
Return air limits may be
used for limiting zone tem
peratures. Continuous fan
operation recommended.
114
COOL RET AIR LIMIT
Cooling Return Air Limit
60.0
65.0
80.0
°F
Return air limit for cooling. If
the return air cooling limit is
exceeded, the cooling de
mands are interrupted.
Parameter 113 must be set
to 1 to enable.
115
HEAT RET AIR LIMIT
Heating Return Air Limit
60.0
85.0
100.0
°F
Return air limit for heating. If
the return air heating limit is
exceeded, the heating de
mands are interrupted.
Parameter 113 must be set
to 1 to enable.
117
DCV MAX DAMPER
OPEN
Demand Control
Ventilation Maximum
Damper Open
0
50
100
%
Maximum allowed demand con
trol ventilation damper open po
sition.
118
DCV DAMP START
OPEN
Demand Control
Ventilation Damper Start
Open
0
700
2000
PPM
Damper “start open" CO
2
set point for Demand Control
Ventilation.
Level where fresh air
damper begins to open.
119
DCV DAMP FULL
OPEN
Demand Control
Ventilation Maximum
Damper Full Open Set
Point
0
1200
2000
PPM
Damper “full open" CO
2
set
point for Demand Control
Ventilation.
Level where fresh air
damper is opened to maxim
um.
120
DCV HI TMP OV FL CL
Demand Control
Ventilation Outdoor Air
Control Hi Temperature
Override Full Closed
-31.0
105.0
132.0
°F
High outdoor air temp. where
fresh air damper is closed to
minimum position.
121
DCV HI TMP OV ST CL
Demand Control
Ventilation Outdoor Air
Control Hi Temperature
Override Start Closing
-31.0
75.0
132.0
°F
High outdoor air temperature
where fresh air damper begins
to close.
122
DCV LO TMP OV FL CL
Demand Control
Ventilation Outdoor Air
Control Low Temperature
Override Full Closed
-31.0
10.0
132.0
°F
Low outdoor air temperature
where fresh air damper is
closed to minimum position
123
DCV LO TMP OV ST CL
Demand Control
Ventilation Outdoor Air
Control Low Temperature
Override Start Closing
-31.0
40.0
132.0
°F
Low outdoor air temp. where
fresh air damper begins to
close.
127
OAC MANUAL RESET
Outdoor Air Control
Manual Reset
0
50
100
%
Manual reset value.