![Lennox PRODIGY2.0 Скачать руководство пользователя страница 28](http://html1.mh-extra.com/html/lennox/prodigy2-0/prodigy2-0_application-manual_1877211028.webp)
28
5.5.2.
Energence B Box Standard, High and Ultra-High Efficiency Units (7.5-, 8.5-, 10-, 12- and 12.5-Ton)
Table 19. Low Ambient Fan Operations (B Box Standard, High and Ultra-High Efficiency Units)
Models
Fan
Associated
Compressor
Low Ambient Control
OD Temp < Parameter 84 (55°F)
LCH, LGH 092H, 102H, 120H, and 150S
1
1, 2
OFF
2
1, 2
On with S11 or S84
LCH, LGH 094U, 122U and 152U
1
1, 2
On with S11
2
1, 2
OFF
3
1, 2
OFF
B BOX
Gas / Electric & Electric / Electric:
LC/LG 094U
7
½
ton
LC/LG 122U
10 ton
LC/LG 152U
12
½
ton
Compressors
A55-K1
A55-K2
1
2
Condenser Fans
CP1 or 2-A55-PWM 3
CP1 or 2-A55-PWM 3
CP1 or 2-A55-PWM 2
2
(B5)
55
°
F
3
(B21)
55
°
F
1
(B4)
S11
1
(B4)
55
°
F
B BOX
Gas / Electric & Electric / Electric:
LC/LG 092H
7 ½ ton
LC/LG 102H
8 ½ ton
LC/LG 120H
10 ton
Condenser Fans
2
(B5)
S11 S84
CP1 or 2-A55-K10
CP1 or 2-A55-K68
A55-K1
A55-K2
Compressors
1
2
LC/LG 150S
12 ton