17. LonTalk
For complete information on how to perform the physical installation of LonTalk
®
, please refer to 506693-01, LonTalk
Module Kit (54M27).
17.1. Setup
To enable the LonTalk module, go to:
1.
SETUP > INSTALL
and run the setup wizard. When
Configuration ID 1
appears on the screen, configure position
5
as
L
.
2. To configure the LonTalk Network, go to:
SETUP > NETWORK INTEGRATION = LONTALK
NOTE
: Additional settings will be required to complete after completing step 2.
17.2. Comfort Sensors
To
enable
the M3 Unit Controller to use Comfort Sensors, use the following procedure:
LonTalk Configuration
1. Go to
SETUP
and select
NETWORK INTEGRATION
.
2. Use the
Adjust and set values
arrows to display
LonTalk
and press the
SAVE
button to continue.
3.
CONTROL MODE
will need to be set to
ROOM SENSOR
. Press the
SAVE
button to continue.
4.
NETWORK SENSOR > CO2
needs to be set to
YES
if needed. Press the
SAVE
button to continue.
5.
NETWORK SENSOR > RELATIVE HUMIDITY
needs be set to
YES
if needed. Press the
SAVE
button to continue.
6.
NETWORK SENSOR > TEMPERATURE
will need to be set to
NO
(mandatory).
NOTE
: Additional settings will be required to complete after completing step 7. Once the above steps are completed the
Comfort Sensor output will be accepted by the system.
L Connection Configuration
1. Go to
SETUP
and select
NETWORK INTEGRATION
.
2. Use the
Adjust and set values
arrows to display
L-CONNECTION
and press the
SAVE
button to continue.
3. Adjust the
L-CONNECTION ADDRESS
if required and press
SAVE
button to continue.
NOTE
: Both the L-Connection address setting and Comfort Sense address setting needs to be exactly the same. In
addition, the Comfort Sense should be configured with NO NCP option.
4.
CONTROL MODE
will need to be set to
ROOM SENSOR
. Press the
SAVE
button to continue.
5.
NETWORK SENSOR > CO2
needs to be set to
YES
if needed. Press the
SAVE
button to continue.
6.
NETWORK SENSOR > RELATIVE HUMIDITY
needs be set to
YES
(mandatory). Press the
SAVE
button to
continue.
7.
NETWORK SENSOR > TEMPERATURE
will need to be set to
YES
(mandatory).
NOTE
: Additional settings will be required to complete after completing step 7. Once the above steps are completed the
Comfort Sensor output will be accepted by the system.
NOTE
: If Comfort Sensor input is still not working, cycle power to the M3 Unit Controller.