Table 57. Menu Interface (Level 1 - SETUP)
Level 2
Level 7
Level 6
Level 5
Level 4
Level 3
NETWORK
INTEGRATION
NETWORK =
L-CONNECTION
LCONN ADDRESS = X
CONTROL MODE
=
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPEATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR
ON-CONTINUOUS 1, 2 OR 3 *
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR
BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
* OCC (OCCUPIED) BLOWER MODE DESCRIPTION
:
AUTO CYCLE: BLOWER CYCLES WITH DEMAND
ON-CONTINUOUS 1: BLOWER IS ON WITH EITHER THE OCCUPANCY SENSOR OR OC
CUPANCY SCHEDULER INDICATES OCCUPIED.
ON-CONTINUOUS 2: BLOWER IS ON ONLY WITH BOTH THE OCCUPANCY SENSOR AND
OCCUPANCY SCHEDULER, BOTH INDICATES OCCUPIED.
ON-CONTINUOUS 3: BLOWER IS ON ONLY WHEN BOTH THE OCCUPANCY SENSOR
AND OCCUPANCY SCHEDULER INDICATES OCCUPIED. IN ADDITION, BLOWER WILL
BE ON A MINIMUM OF 25% OF THE TIME WHEN OCCUPANCY SCHEDULER INDICATES
OCCUPIED HOWEVER THE OCCUPANCY SENSOR INDICATES NOT OCCUPIED. THE
25% MINIMUM IS ACHIEVED BY TURNING BLOWER ON FOR 30 MINUTES AND OFF FOR
90 MINUTES.
NETWORK = BACNET
BACNET MAC ADDRESS = X
BACNET BAUD RATE = 9.6, 19.2, 38.4 OR 76.8 K
CONTROL MODE =
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR
ON-CONTINUOUS 1, 2 OR 3 (SEE DESCRIPTION ABOVE)
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR
BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK = LONTALK
CONTROL MODE =
ROOM SENSOR, MON
ITOR ONLY OR NET
WORK THERMOSTAT
NETWORK SENSOR CO2 = YES OR NO
NETWORK SENSOR RELATIVE HUMIDITY = YES OR NO
NETWORK SENSOR TEMPERATURE = YES OR NO
ROOM SENSOR OCC BLOWER MODE= AUTO CYCLES OR
ON-CONTINUOUS 1, 2 OR 3 (SEE DESCRIPTION ABOVE)
BACKUP MODE = NONE, ROOM SENSOR, RETURN AIR
BACKUP OR THERMOSTAT
BACKUP SETPOINTS OCCUPIED HEAT = XX.X F
BACKUP SETPOINTS UNOCCUPIED HEAT = XX.X F
BACKUP SETPOINTS OCCUPIED COOL = XX.X F
BACKUP SETPOINTS UNOCCUPIED COOL = XX.X F
NETWORK = RTU
STANDALONE
BACKUP MODE =
NONE OR RETURN AIR
BACKUP
SETPOINTS HEAT = XX.X F
SETPOINTS COOL = XX.X F