Table 59. Menu Interface (Level 1 - SETTINGS)
NOTE
: AVAILABLE MENU OPTIONS ARE DEPENDENT ON HARDWARE CONFIGURATION. USE THE
ADJUST AND SET VALUES
ARROWS
TO SCROLL UP OR DOWN FOR SELECTION OPTIONS.
Level 2
Level 7
Level 6
Level 5
Level 4
Level 3
RTU OPTION
DAMPER
ECONOMIZER ENTHALPY OFFSET = X MA
ECONOMIZER TEMP ECON TYPE = TEMPERATURE OFFSET OR TEMPERATURE SETPT
ECONOMIZER OAT SETPOINT = XX.X F
FREE COOLING SUPPLY AIR SETPOINT = XX F
OUTDOOR AIRFLOW = XXX CFM
ADVANCED AIRFLOW ALARMS = EN
ABLED OR DISABLED
(ONLY VISIBLE IF
CONFIGURATION ID 1, POSITION 2 IS SET
CORRECTLY).
ADV AIRFLOW ALARMS LO SPLY AIRFLOW ALM
= XX%
ADV AIRFLOW ALARMS LO OD AIRFLOW ALM =
XX%
ADV AIRFLOW ALARMS HI OD AIFLOW ALM =
XX%
ADV AIRFLOW ALARMS ALM TRIGGER PERIOD =
XXXX SEC
MIN DAMPER POSITION BLOWER ON HIGH = X.X %
MIN DAMPER POSITION BLOWER ON LOW = X.X %
VENTILATION OPTIONS
DEMAND CONTROL VENTILATION
BUILDING PRESSURE CONTROL
IF DCV
DEMAND CONTROL VENT DAMPER START
OPEN = XXXX.X PPM
DEMAND CONTROL VENT DAMPER FULL OPEN
= XXXX.X PPM
DEMAND CONTROL VENT
>
DAMPER MAX OA
CFM = X CFM
(ONLY VISIBLE IF CONFIGURATION ID 1, POSI
TION 2 IS SET CORRECTLY).
DEMAND CONTROL VENT DAMPER MAX OPEN
ING = XXX.X%
IF BPC
BUILDING PRESS CTRL > PRESSURE SETPOINT
= X.X IN H20
OUTDOOR AIR CONTROL
(ONLY VISISBLE
IF CONFIGURATION ID 1, POSITION 8 IS
SET CORRECTLY)
VELOCITY SETPOINT = XXX FT/MIN
POWER EXHAUST ON BY ECON TRAVEL = XX.X %
FRESH AIR
HEATING ENABLE
FAH = YES OR NO
FRESH AIR HEATING FAH SETPOINT = XX F
FRESH AIR
COOLING ENABLE
AFC = YES OR NO
FRESH AIR COOLING AFC SETPOINT = XX F