![Lennox PRODIGY2.0 Скачать руководство пользователя страница 69](http://html1.mh-extra.com/html/lennox/prodigy2-0/prodigy2-0_application-manual_1877211069.webp)
69
16.5. Analog Value Objects
Optional Properties Supported:
None
Optional Writable Properties:
Present_Value
Table 42. Analog Value Objects List
Object
ID
Object Name
Units
Min.
Value
Max.
Value
Valid Values within
Range
Note
1
Baud Rate Setting
None
9600
76800
9600, 19200, 38400,
76800
38400 default
130
Heating Occupied Set
Point
°F
40
95
All
For occupied and unoccupied set
points considered separately, the heat
ing set point must be lower than the
cooling set point by at least the
auto−changeover dead band value set
in M3 unit controller parameter 152 (de
fault 3ºF).
131
Cooling Occupied Set
Point
°F
40
95
All
132
Heating Unoccupied
Set Point
°F
40
95
All
133
Cooling Unoccupied
Set Point
°F
40
95
All
134
Supply Airflow Low
Speed Target
CFM
Refer to parameter labels on unit or refer to unit
installation instruction or service manual.
1. These objects are applicable only if
Advanced Airflow (Smart Airflow
®
) is
installed in the system.
2. Object IDs 136 and 137 are not ap
plicable to an Energence Standard Effi
cient 3 to 6-ton units.
3. Multiply the tonnage of the RTU with
the value in CFM/ton to derive the value
in CFM units.
135
Supply Airflow High
Speed Target
CFM
136
Supply Airflow Medi
um Low Speed Target
CFM
137
Supply Airflow Medi
um High Speed Target
CFM
138
Supply Airflow Heat
Mode Target
CFM
139
Ventilation Airflow
Target
CFM
140
Smoke Airflow Target
CFM
141
Outdoor Airflow Target
CFM
0 cfm/
ton
150 cfm/
ton
All
CFM = cubic feet minute