111
25.2. Configuration ID 1
CONFIGURATION ID 1
Humiditrol [1]
Not Installed =
N
Humiditrol Installed =
H
Unconfigured =
U
Economizer [2]
Not Installed =
N
Motorized Outdoor Air
Damper Only =
M
Economizer - Temperature =
T
Economizer Global =
G
Economizer - Single
Enthalpy =
S
Economizer - Dual Enthalpy =
D
Unconfigured =
U
Power Exhaust [3]
Not Installed =
N
Single-Stage =
S
Dual-Stage =
D
Variable Speed Drive =
V
Unconfigured =
U
Power Exhaust Control [4]
Not Installed =
N
Damper Position =
A
S37 Pressure Switch =
B
A34 Pressure Sensor =
C
A34 Pressure Sensor with
Enable Switch =
D
S27 and S39 Pressure
Switch =
E
[5] Network Module
N
= Not Installed
B
=
BACnet
L
= LonTalk (Lennox)
[6] Blower Variable
Frequency Drive Bypass
N
= Not Installed
A
=
Automatic Bypass
M
= Manual Bypass
U
= Electronic Bypass Field
Un-configured
[7] Advanced Air Flow
Control System
N
= Not Installed
S
=
Installed with Standard
Economizer
L
= Installed with High Performance
Economizer
U
= Unconfigured
[8] Outdoor Air CFM Control
N
= Not applicable (for future use)
L
= Outdoor Air Control Installed
with A24 Sensor set for low range.
M
= Outdoor Air Control Installed
with A24 Sensor set for medium
range.
H
= Outdoor Air Control Installed
with A24 Sensor set for high
range.
IMPORTANT
: Always refer to the white sticker titled ORIGINAL FACTORY UNIT CONFIGURATION located inside the control box area.
NOTE
: The M3 unit controller will display applicable alarm(s) if any positions is left unconfigured (U).
1 2 3 4 5 6 7 8
Figure 35. Configuration ID 1