Table 63. M3 Control Parameters
Control Parameter
Control Value
Units
Description
No
Screen Name
Parameter Short
Description
Min.
Default
Max.
2
LANGUAGE
LANGUAGE
= ENGLISH,
ESPA (SPAN
ISH) or FRAN
(FRENCH)
Option
Select desired language for
user interface. Options are Eng
lish, French and Spanish.
Power and Damper Parameters
5
VAV CONTROL MODE
Variable Air Volume
Control Mode
0
If applicable to
specific unit,
see unit
parameter label
for default
setting
511
Option
Applicable to Energence Stan
dard Efficiency 3- to 6-ton units
only.
16 - Runs the blower in high
speed when occupied and
there is not other active
demand (room sensor
mode only)
32 - Runs the blower in high
speed when G is active and
there is no other active de
mand (thermostat mode
only)
6
BLOWER SMOKE
OUTPUT
Blower Smoke Output
20.0
Check unit label
as parameters
may be
configured to
order.
100.0
%
Applicable to Energence
Standard Efficiency 3- to
6-ton units only.
Blower staged percentage
output during smoke detec
tion.
7
BLOWER HEAT
OUTPUT
Blower Heat Output
20.0
100.0
%
Applicable to Energence
Standard Efficiency 3- to
6-ton units only.
Blower staged percentage
output high speed; used for
heating and high cooling or
ventilation.
8
BLOWER COOL
OUPUT
Blower Cool Output
20.0
100.0
%
Applicable to Energence
Standard Efficiency 3- to
6-ton units only.
Blower staged percentage
output low speed; used for
low cooling or ventilation.
9
MIN DAMPER LOW
BLWR
Minimum Damper
Position During High
Speed Blower Operation
0.0
0.0
100.0
%
Minimum damper position
during low speed blower op
eration.
Use parameter 132 during
high speed blower operation
10
FREE CL STG UP DLY
Free Cooling Blower
Stage Up Delay
0
300
1800
Sec
Applicable to Energence
Standard Efficiency 3- to
6-ton units only.
Free cooling blower stage-
up delay. Blower runs low
speed during delay, and then
shifts to high speed.
11
ENBL FIELD STAT RPT
Enabled Field Status
Report
0 = OFF
1 = ON
Option
Enabled Field Status Report