LENNOX MERIT

®

 SERIES B-VENT GAS FIREPLACES   •   36" LMBV MODELS   •   CARE AND OPERATION INSTRUCTIONS

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM

1.

  Spark ignitor will not light 

pilot after repeated triggering 

of ignitor button.

2.

  Pilot will not stay lit after 

carefully following the light-

ing instructions.

3.

  Pilot burning, no gas to 

burner, Valve knob “ON,” 

Wall Switch “ON.”

4.

  Frequent pilot/burner outage 

problem.

CORRECTIvE ACTION

SymPTOm

A.

  Defective ignitor

  (no spark at electrode).

b.

  Defective or misaligned electrode 

at pilot (spark at electrode).

C.

  Gas supply pressure errant.

D.

  Pilot orifice plugged.

A.

  Defective pilot generator (thermo-

generator).

A. 

 Damper closed or Damper Switch 

defective.

b.

  Wall switch or wires defective.

C.

  Thermopile may not be generating 

sufficient millivoltage.

D.

  Plugged burner orifice.

A.

  Pilot flame may be too low or 

blowing (high) causing the pilot/

valve safety to drop out.

Check for spark at electrode and pilot; if no spark and electrode 

wire is properly connected, replace ignitor.

Using a match, light pilot. If pilot lights, turn off pilot and 

trigger the ignitor button again. If pilot lights, an improper 

gas  mixture  caused  the  bad  lighting  and  a  longer  purge 

period is recommended. If pilot will not light – check gap at 

electrode and pilot - should be 1/8" to have a strong spark. 

If gap measures 1/8", replace pilot (Figure 9

 

).

Check inlet gas pressure. It should be within the limits as 

marked on the rating plate.

Clean or replace pilot orifice.

Check pilot flame, it must impinge on thermogenerator (Figure 

9 ). Clean and/or adjust pilot for maximum flame impingement 

on thermogenerator. Ensure that the connection between the 

valve and thermogenerator are tight and secure.

Ensure damper control lever is locked in the open position, 

all the way to the right.  If the damper control lever is locked 

in the open position troubleshoot through Steps B., C. and D. 

below.  If the main burner will still not light, determine if the 

damper switch is defective and replace if necessary.

Check wall switch and wires for proper connections. Jumper 

wire across terminals at wall switch, if burner comes on, 

replace defective wall switch. If okay, jumper wires across 

wall switch wires at valve, if burner comes on, wires are faulty 

or connections are bad.

Check thermopile with millivolt meter. Take reading at ther-

mopile terminals of gas valve. Should read 325 millivolts 

minimum  with  optional  wall  switch  “OFF.”  Replace  faulty 

thermopile if reading is below specified minimum.

Check burner orifice for stoppage and remove.

Clean and/or adjust pilot flame for maximum flame impinge-

ment on thermogenerator (Figure 9 ).

POSSIblE CAUSES

Note: Before troubleshooting the gas control system, be sure external gas shut off valve (located at gas supply inlet) is in 

the “ON” position.

Important: Valve system troubleshooting should only be accomplished by a qualified service technician.

Содержание Merit LMBV-36REN

Страница 1: ...on ou pour viter tout dommage mat riel toute blessure ou la mort This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by...

Страница 2: ...ns and cleanings may be required due to excessive lint from carpeting bedding material etc It is imperative that the control compartment burners and circulating airpassagewaysoftheappliancebekeptclean...

Страница 3: ...g are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Turn off the gas sup ply to the appliance and have it serviced by a qualified profe...

Страница 4: ...tructions respectively Millivoltandelectronicappliance lighting instructions may also be found on the pulloutlabelsattachedtothegascontrolvalve located within the gas control compartment If your appli...

Страница 5: ...ed Thedamperleveractuatesaswitch seewiring diagram which will prevent the appliance main burnerfromlightingunlessthedamperislocked open The appliance flue damper must always remain open when operating...

Страница 6: ...la casa 2 Si se usa un control remoto para controlar la chimenea encuentre el transmisor y l mpielo bien para quitar el polvo y aceite Pegue la etiqueta en la superficie del transmisor Figura B Selecc...

Страница 7: ...performed Important Turn off gas and any electrical power before servicing the appliance Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in...

Страница 8: ...eaning Burner Logs and Controls Check Flame Patterns and Flame Height Inspecting Cleaning Pilot and Burner Checking Vent System Appliance Checkout Replacing Rockwool Ember Materials Qualified Service...

Страница 9: ...y hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Turnoffallelectricitytotheap pliance before you install grate and logs Warning This appliance is...

Страница 10: ...ment Only If any of the original wire as supplied must be replaced it must be replaced with Type AWM 200 C 18 GA wire Thermopile TH TP TH TP Limit Switch Damper Switch BK BK BK BK WHT 1 If any of the...

Страница 11: ...ontinue to hold the control knob in for about 1 minutes after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out repeat steps 5 through 8 If knob does not pop...

Страница 12: ...en utilisant le t l phone du voisin S il vous est impossible de contacter votre compagnie de gaz appelez le service des incendies C N utilisez que votre main pour manipuler le bouton de r glage du gaz...

Страница 13: ...ian to inspect the appliance and to replace any part of the control system and any gas control which has been under water Lighting Instructions Electronic 1 For complete shut down turn remote wall swi...

Страница 14: ...te plaque 2 Tournez l interrupteur mural la position d arr t OFF 3 Ouvrez la porte du compartiment de contr le du bas 4 Assurez vousquelasoupaped arr tdelacanalisationprincipale est ouverte 5 Tournez...

Страница 15: ...gap measures 1 8 replace pilot Figure 9 Check inlet gas pressure It should be within the limits as marked on the rating plate Clean or replace pilot orifice Checkpilotflame itmustimpingeonthermogenera...

Страница 16: ...sition Disconnect Control Harness Set Thermostat To Call For Heat Check For Proper Voltage At Control Harness See Insert A Voltage Should Be 24V Between Thermostat Or Pressure Switch And 24V Common An...

Страница 17: ...iance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions concerning the installation o...

Страница 18: ...as been sent The Model RCL is designed to operate with all millivolt ignition systems as well as electronic ignition systems It may be installed with use for either natural or propane gas appliances T...

Страница 19: ...4L58 1 24 Piezo Ignitor 10K86 1 10K86 1 25 Ignition Cable H5047 1 H5047 1 26 Pilot Tube 74L56 1 74L56 1 Natural Propane No DESCRIPTION Part No Qty Part No Qty Gas Fireplace Assembly 1 Firescreen H4167...

Страница 20: ...23 21 REF 10 26 22 24 25 14 14 REF 9 15 Printed in U S A 2006 by Lennox Hearth Products P N 875033M REV C 07 2010 Lennox Hearth Products reserves the right to make changes at any time without notice...

Отзывы: