background image

2

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX MERIT

®

 SERIES B-VENT GAS FIREPLACES   •   36" LMBV MODELS   •   CARE AND OPERATION INSTRUCTIONS

TAblE OF CONTENTS

Introduction ......................................page  2
General Information ..........................page  2
Operation/Care of Your Appliance .....page  3
Damper & Outside Air Controls .........page  4
Manual Limit Switch .........................page  5
Maintenance ......................................page  6
Millivolt Appliance Checkout .............page  6

Attaching "Safety-in-Operation"
    Warnings ............................ page  6

Electronic Appliance Checkout ..........page  7
Maintenance Schedule ......................page  8
Log and Rockwool Placement ...........page  9
Wiring Diagrams ...............................page  10
Lighting Instructions – Millivolt ........page  11
Lighting Instructions – Electronic .....page  13
Troubleshooting Guide – Millivolt......page  15
Troubleshooting Guide – Electronic ..page  16
Warranty ...........................................page  17
Product Reference Information .........page  17
Replacement Parts ............................page  17
Accessory Components ....................page  18
Replacement Parts List .....................page  19

These appliances are designed to operate on 

natural or propane gas only. The use of other 

fuels or combination of fuels will degrade the 

performance of this system and may be dan-

gerous.

CONGRATUlATIONS!

In selecting this LENNOX B-vented gas appliance, you have chosen one of the finest 

and most dependable fireplaces available. This gas fireplaces is a beautiful, prestigious 

alternative to a wood burning fireplace.  Welcome to a family of tens of thousands of 

satisfied LENNOX fireplace owners.
Please read and carefully follow all of the instructions found in this manual.  Please 

pay special attention to the safety instructions provided in this manual.  The Care and 

Operation Instructions included herein will help to ensure many years of dependable and 

enjoyable service from your LENNOX product.

INTRODUCTION

The millivolt appliances are designed to operate 

on either natural or propane gas. A millivolt gas 

control valve with piezo ignition system provides 

safe, efficient operation.
The  electronic  appliances  are  designed  to 

operate on either natural or propane gas. An 

electronic intermittent ignition system provides 

safe,  efficient  operation.  External  electrical 

power is required to operate these units.
These appliances comply with National Safety 

Standards and are tested and listed by Warnock 

Hersey (Report No. 3106807) to ANSI Z21.50 

- latest edition (in Canada, CSA 2.22 - latest 

edition), and CAN/CGA-2.17-M91 in both USA 

and Canada, as vented gas fireplaces.
Installation  must  conform  to  local  codes.  In 

the absence of local codes, installation must 

comply with the current National Fuel Gas Code, 

ANSI Z223.1 (NFPA 54). (In Canada, the current 

CAN/CGA  B149  installation  code.)    Electrical 

wiring must  comply with local codes.   In the 

absence of local codes, installation must be in 

accordance with the National Electrical Code, 

NFPA 70 - (latest edition). (In Canada, the current 

CSA C22.1 Canadian Electric Code.)

GENERAl INFORmATION

Note:  Installation  and  repair  should  be  per-

formed  by  a  qualified  service  person.  The 

appliance should be inspected annually by a 

qualified professional service technician. More 

frequent  inspections  and  cleanings  may  be 

required due to excessive lint from carpeting, 

bedding material, etc. It is imperative that the 

control compartment, burners and circulating 

air passage ways of the appliance be kept clean.
S'assurer que le brùleur et le compartiment des 

commandes sont propres.  Voir les instructions 

d'installation et d'utilisation qui accompagnent 

l'apareil.
Provide adequate clearances around air open-

ings and adequate accessibility clearance for 

service and proper operation. Never obstruct 

the front openings of the appliance.
Due to high temperatures the appliance should 

be located out of traffic and away from furniture 

and draperies.  Locate furniture and window 

coverings accordingly.

  Gas 

Orifice  

  Type 

Size 

Elevation

 

 

 

0 - 4500'

 

 

 

(0 - 1370 m)

 

 

 

0 - 4500'

 

 

 

(0 - 1370 m)

Natural

Propane

(.058)

#42

(.0935)

WARNING:  THESE  FIREPlACES  ARE 

vENTED DECORATIvE GAS APPlIANCES.  

DO NOT bURN WOOD OR OTHER mATE-

RIAl IN THESE APPlIANCES.

Nominal operating pressures for the manifold 

side of the gas control system are; 3.5 inches 

water column (0.87 kPa) for natural gas models 

and  10  inches  water  column  (2.49  kPa)  for 

propane gas models. 
Test gage connections are provided on the front 

of the millivolt gas control valve (identified E 

for the inlet and A for the manifold side,  see 

Figure 2 ).  A 1/8" NPT test gage connection 

is provided at the inlet and manifold side of   

the electronic gas control valve (Figure 3 ).  
Minimum inlet gas pressure to the appliance is 

4.5 inches water column (1.24 kPa) for natural 

gas and 11 inches water column (2.74 kPa) for 

propane for the purpose of input adjustment.
Maximum inlet gas supply pressure to the ap-

pliance is 10.5 inches water column (2.62 kPa) 

for natural gas and 13.0 inches water column 

(3.23 kPa) for propane.
The appliance must be isolated from the gas 

supply piping system (by closing its individual 

manual  shut-off  valve)  during  any  pressure 

testing  of  the  gas  supply  piping  system  at 

test pressures equal to or less than 1/2 psig 

(3.5 kPa).
The appliance and its individual shut-off valve 

must  be  disconnected  from  the  gas  supply 

piping system during any pressure testing of 

that system at pressures in excess of 1/2 psig 

(3.5 kPa).
These appliances must not be connected to a 

chimney or flue serving a separate solid fuel 

burning appliance.

Input of appliance is 24,000 BTU/HR.

       

WARNING

B-Vent appliances are not designed 

to operate in negatively pressured 

environments  (pressure  within 

the home is less than pressures 

outside).  Significant  negatively 

pressured  environments  caused 

by  weather,  home  design,  or 

other  devices  may  impact  the 

operation  of  these  appliances. 

Negative pressures may result in 

poor flame appearance, sooting, 

damage to property and/or severe 

personal  injury.  Do  not  operate 

these  appliances  in  negatively 

pressured environments.

       WARNING 

Improper installation, adjustment, 

alteration, service or maintenance 

can  cause  injury  or  property 

damage.  Refer to this manual.  For 

assistance or additional informa-

tion consult a qualified installer, 

service agency or the gas supplier.

DO  NOT  ATTEmPT  TO  AlTER  OR  mODIFy  

THE CONSTRUCTION OF THE APPlIANCE OR 

ITS  COmPONENTS.  ANy  mODIFICATION  OR 

AlTERATION  mAy  vOID  THE  WARRANTy,  

CERTIFICATION AND lISTINGS OF THIS UNIT.

Содержание Merit LMBV-36REN

Страница 1: ...on ou pour viter tout dommage mat riel toute blessure ou la mort This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by...

Страница 2: ...ns and cleanings may be required due to excessive lint from carpeting bedding material etc It is imperative that the control compartment burners and circulating airpassagewaysoftheappliancebekeptclean...

Страница 3: ...g are similar to the flu with headaches dizziness and or nausea If you have these signs obtain fresh air immediately Turn off the gas sup ply to the appliance and have it serviced by a qualified profe...

Страница 4: ...tructions respectively Millivoltandelectronicappliance lighting instructions may also be found on the pulloutlabelsattachedtothegascontrolvalve located within the gas control compartment If your appli...

Страница 5: ...ed Thedamperleveractuatesaswitch seewiring diagram which will prevent the appliance main burnerfromlightingunlessthedamperislocked open The appliance flue damper must always remain open when operating...

Страница 6: ...la casa 2 Si se usa un control remoto para controlar la chimenea encuentre el transmisor y l mpielo bien para quitar el polvo y aceite Pegue la etiqueta en la superficie del transmisor Figura B Selecc...

Страница 7: ...performed Important Turn off gas and any electrical power before servicing the appliance Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in...

Страница 8: ...eaning Burner Logs and Controls Check Flame Patterns and Flame Height Inspecting Cleaning Pilot and Burner Checking Vent System Appliance Checkout Replacing Rockwool Ember Materials Qualified Service...

Страница 9: ...y hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Turnoffallelectricitytotheap pliance before you install grate and logs Warning This appliance is...

Страница 10: ...ment Only If any of the original wire as supplied must be replaced it must be replaced with Type AWM 200 C 18 GA wire Thermopile TH TP TH TP Limit Switch Damper Switch BK BK BK BK WHT 1 If any of the...

Страница 11: ...ontinue to hold the control knob in for about 1 minutes after the pilot is lit Release knob and it will pop back up Pilot should remain lit If it goes out repeat steps 5 through 8 If knob does not pop...

Страница 12: ...en utilisant le t l phone du voisin S il vous est impossible de contacter votre compagnie de gaz appelez le service des incendies C N utilisez que votre main pour manipuler le bouton de r glage du gaz...

Страница 13: ...ian to inspect the appliance and to replace any part of the control system and any gas control which has been under water Lighting Instructions Electronic 1 For complete shut down turn remote wall swi...

Страница 14: ...te plaque 2 Tournez l interrupteur mural la position d arr t OFF 3 Ouvrez la porte du compartiment de contr le du bas 4 Assurez vousquelasoupaped arr tdelacanalisationprincipale est ouverte 5 Tournez...

Страница 15: ...gap measures 1 8 replace pilot Figure 9 Check inlet gas pressure It should be within the limits as marked on the rating plate Clean or replace pilot orifice Checkpilotflame itmustimpingeonthermogenera...

Страница 16: ...sition Disconnect Control Harness Set Thermostat To Call For Heat Check For Proper Voltage At Control Harness See Insert A Voltage Should Be 24V Between Thermostat Or Pressure Switch And 24V Common An...

Страница 17: ...iance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions concerning the installation o...

Страница 18: ...as been sent The Model RCL is designed to operate with all millivolt ignition systems as well as electronic ignition systems It may be installed with use for either natural or propane gas appliances T...

Страница 19: ...4L58 1 24 Piezo Ignitor 10K86 1 10K86 1 25 Ignition Cable H5047 1 H5047 1 26 Pilot Tube 74L56 1 74L56 1 Natural Propane No DESCRIPTION Part No Qty Part No Qty Gas Fireplace Assembly 1 Firescreen H4167...

Страница 20: ...23 21 REF 10 26 22 24 25 14 14 REF 9 15 Printed in U S A 2006 by Lennox Hearth Products P N 875033M REV C 07 2010 Lennox Hearth Products reserves the right to make changes at any time without notice...

Отзывы: