background image

Page 19

LRP14AC / LRP14HP

Condensate Drain

This package unit is equipped with a 3/4” FPT coupling 

for condensate line connection. Plumbing must conform 

to local codes. Use a sealing compound on male pipe 

threads.

Do not 

operate unit without a drain trap. The condensate 

drain is on the negative pressure side of the blower; 

therefore, air being pulled through the condensate line will 

prevent positive drainage without a proper trap.

The condensate drain line must be properly trapped, 

routed to a suitable drain and primed prior to unit 

commissioning.

 

NOTE

Install drain lines and trap so they do not block 

service access to the unit.

See Figure 5 for proper drain arrangement. The drain line 

must pitch to an open drain or pump to prevent clogging 

of the line.  Seal around the drain connection with suitable 

material to prevent air leakage into the return air system. 

To prime trap, pour several quarts of water into drain, 

enough to fill drain trap and line. 

Drain lines should be hand-tightened only. Do not use 

tools to tighten fitting into drain.

CAUTION

Minimum Pitch: 

1 in (25) Per 10” 

(3048 mm) of 

Line

Open 

Vent

Unit

Trap must be deep enough to offset maximum static difference 

(generally, 3 inches (76 mm) minimum). In addition, the drain line 

must be supported if longer than 10 feet.

Trap must be primed at start-up.

Mounting 

Frame

Figure 9. Typical Condensate Drain Connection

Crankcase Heater (if used)

Some models may be equipped with a crankcase heater 

to prevent excessive migration of liquid refrigerant into the 

compressor during off cycles. Power must be maintained 

to the unit to keep this feature active.

Except as required for safety while servicing, 

do not open 

the system disconnect switch.

Heater Kit Accessory (if used)

The unit is fully equipped for cooling operation without 

auxiliary heat. A heater kit accessory may also be used. To 

install the heater kit accessory (see Figure 7):

1.  Disconnect the power and open the main control 

access.

2.  Disconnect the plug separating the high voltage wire 

harness. Remove the high voltage wire harness plug 

and discard.

3. 

Remove  the  heater  blockoff  by  removing  the  four 

screws holding it in place.

4.  Insert the heater into the control panel and fasten in 

the same mounting holes.

5.  Plug the heater wiring harness into the wire harness 

on the control assembly. Field wiring of the auxiliary 

heater is separate from the unit power supply. Wire the 

power supply wiring for the heater to the appropriate 

connections on the heater kit.

Sequence of Operation

Cooling

When the thermostat is in the cooling mode, the O circuit 

is powered, which energizes the reversing valve. Upon 

cooling demand, the thermostat closes circuit R and Y. 

Closing R and Y closes the unit contactor, starting the 

compressor and outdoor fan. The thermostat automatically 

closes the R to G circuit, which brings on the indoor blower 

at the same time. Upon satisfying cooling demand, the 

thermostat will open the above circuits and open the main 

contactor, stopping the compressor and outdoor fan. If the 

unit is equipped with a delay timer, the blower will continue 

to operate for 60 to 90 seconds, which improves system 

efficiency.

Heating - Heat Pump Stage

Upon heating demand, the thermostat closes circuit R to 

Y, which closes the unit contactor, starting the compressor 

and outdoor fan. The reversing valve is not energized in 

the heating mode. The thermostat again automatically 

brings on the indoor fan at the same time. Upon satisfying 

heating demand, the thermostat opens above circuits and 

stops unit operation.

Heating - Auxiliary Electric Heat

Upon heating demand for auxiliary electric heat, the 

thermostat closes circuit R to W, which energizes the 

Содержание LRP14AC Series

Страница 1: ...LRP14AC LRP14HP 22 Wiring Diagrams LRP14AC LRP14HP 24 2021 Lennox Industries Inc Dallas Texas USA WARNING Improper installation adjustment alteration service or maintenance can cause property damage p...

Страница 2: ...13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY GAS...

Страница 3: ...RY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49 2 39 2...

Страница 4: ...1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 330 3 76...

Страница 5: ...76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bottom e...

Страница 6: ...Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 ADJUSTABLE PITCH ROOF CURB Usage A B C in mm in mm in mm 24 30 36 42 7 8 1089 13 7 8 352 16 7 8 429 42 48 60 51 3 8 1305 19 1 2 495 19 1 2 495 NOTE Roof dec...

Страница 7: ...arate request for inspection by the carrier s agent should be made in writing Location Use the following guidelines to select a suitable location for these units 1 Unit is designed for outdoor install...

Страница 8: ...t condenser air discharge outlet combustion air inlet or vent outlet Clearance to Combustibles Clearance for Service Access Front of unit 0 in 24 in Back of unit 0 in 0 in Left side 0 in 24 in Right s...

Страница 9: ...lated Vent Hood Installation The unit is shipped with the vent hood inside the control compartment Locate the vent hood and attach to side of utility panel with screws provided in the instruction bag...

Страница 10: ...SI Z223 1 latest edition or CAN CGA B149 1 2 Canadian Installation Codes to correct improper operation of common venting system Duct System The duct system should be designed and sized according to th...

Страница 11: ...ly upstream of the gas supply connection to the furnace Gas Connection The gas supply line is routed through the gas entry location on the side of the unit see Figure 4 A grommet is provided in the in...

Страница 12: ...adian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C minimum Run the 208 or 230 volt 60 hertz electric power supply...

Страница 13: ...uld be used to connect the thermostat to the unit Heating Start Up For Your Safety Read Before Lighting Furnace is equipped with a direct ignition control Do not attempt to manually light the burners...

Страница 14: ...he gas can be obtained from the local utility BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution For example by actual measurement it takes 38 seconds for the hand on...

Страница 15: ...inuous Fan With the proper thermostat and sub base continuous blower operation is possible by closing the R to G circuit Cooling blower delay is also functional in this mode 5 To change orifice a Remo...

Страница 16: ...dequate airflow occurs This closes the main gas valve Pressure Switch If the combustion air blower should fail the pressure switch prevents the spark electrode and gas valve from being energized Maint...

Страница 17: ...rder they were removed in Steps 1 through 3 10 When replacing the flue collector box be careful so as not to tear the adjoining insulation 11 Assure that all joints on the vent side of the combustion...

Страница 18: ...Page 18 Figure 8 Wiring Diagram Single Phase CT Wiring Diagram LRP14GE...

Страница 19: ...unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 7 1 Disconnect the power and open the main co...

Страница 20: ...from normal heating operation to defrost mode and back During the compressor cycle call for defrost the control accumulates compressor run time at 30 60 90 minute field adjustable intervals If the def...

Страница 21: ...pressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compressor is o...

Страница 22: ...16 3 5 Ton 22 4 Ton 22 5 Ton 5 Based on outdoor ambient temperature of 82 F and indoor entering air of 80 F db 67 F wb Table 8 Heat Pump Cooling System Performance Values Model Liquid Subcooling 2 2 T...

Страница 23: ...432 457 483 36 250 275 301 326 336 351 375 399 423 446 470 493 42 248 271 293 316 325 339 362 385 411 436 462 487 48 265 286 308 329 338 352 376 400 427 455 482 509 60 256 276 296 316 324 340 365 386...

Страница 24: ...WHT GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE...

Страница 25: ...will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has al...

Отзывы: