background image

Page 15

A combustion air inducer operates for the first 10 seconds 

of every cooling cycle to prevent insects from nesting in 

the flue outlet.

Blower Delay – Cooling

The circulating air blower is controlled by a timing circuit 

in the integrated blower/ignition control. Timings are not 

adjustable. Blower “ON” delay is 5 seconds after the 

compressor starts and blower “OFF” timing is 60 seconds 

after the compressor shuts down.

NOTE

There is no blower OFF delay when there is a call 

for G (fan only).

Cooling System Performance

This equipment is a self-contained, factory-optimized 

refrigerant system. The unit should not require adjustments 

to system charge when properly installed. If unit 

performance is questioned, perform the following checks.

Cooling System Performance Values

Model 

Suction 

Sup/- 3°

Liquid 

Subc/- 2°

2 Ton

13

2.5 Ton

16

3 Ton

14

3.5 Ton

14

4 Ton

16

5 Ton

17

Based on outdoor ambient temperature of 82°F, and indoor 

entering air of 80°F db, 67°F wb.

Table 3. 

Ensure unit is installed per manufacturer’s instructions and 

that line voltage and air flow are correct. Refer to Table 3 

for proper performance value. The indoor metering device 

varies by model. When checking performance of a unit 

using an orifice for metering, refer to the suction superheat 

value to judge performance. When checking performance 

of a unit that uses an expansion valve for metering, refer 

to the subcooling value to judge system performance. If 

the measured performance value varies from table value 

allowance, check internal seals, service panels and duct 

work for air leaks, as well as restrictions and blower 

speed settings. If unit performance remains questionable, 

remove system charge, evacuate to 500 microns, and 

weigh in refrigerant to nameplate charge. It is critical that 

the exact charge is re-installed. Failure to comply will 

compromise system performance. If unit performance is 

still questionable, check for refrigerant-related problems, 

such as blocked coil or circuits, malfunctioning metering 

device or other system components.

Continuous Fan

With the proper thermostat and sub-base, continuous 

blower operation is possible by closing the R to G circuit. 

Cooling blower delay is also functional in this mode.

5. 

To change orifice:

a.  Remove screws that fasten the manifold to the 

burner box assembly and remove the manifold.

b. 

Remove  the  orifices,  then  install  replacement 

orifices.

c.  To reassemble: Reverse above steps, making 

sure orifices are inserted into the orifice holders 

on the back end of the burners, and that burners 

are level and centered on each burner opening in 

the vest panel.

6.  To remove or service burners:

a.  Label and disconnect the wires to the rollout switch 

and disconnect the igniter and flame sensor leads 

at the ignition control.

b.  Remove the screws that secure the burner box 

assembly to the vest panel and remove the 

assembly from the unit.

c.  Remove the screws that fasten the burner rack 

and bottom shield assembly to the burner box. 

Burners are now accessible for removal.

d.  To Reassemble: Reverse above steps.

7.  After reassembly of all parts is complete and all wires 

are reconnected, open the main manual gas shutoff 

valve; check for and correct any gas leaks. Turn 

electrical power on, initiate a call for heat, and check 

for proper burner operation.

8.  Install burner access panel.

Heat Anticipator 

The heat anticipator setting is 0.75 amp

. It is important 

that the anticipator setpoint be correct. Too high of a setting 

will result in longer heat cycles and a greater temperature 

swing in the conditioned space. Reducing the value below 

the correct setpoint will give shorter “ON” cycles and 

may result in the lowering of the temperature within the 

conditioned space.

Operation – Gas / Electric Units

Cooling System

The cooling system is factory-charged with HFC-R-410A. 

The compressor is hermetically sealed and base-mounted 

with rubber-insulated bolts.

Cooling Sequence of Operation

When the thermostat calls for cooling, R is closed to Y (see 

the wiring diagrams). This action completes the low voltage 

control circuit, energizing the compressor, condenser fan 

motor, and blower motor.

Unit compressors have internal protection. In the event there 

is an abnormal rise in the temperature of the compressor, 

the protector will open and cause the compressor to stop.

Содержание LRP14AC Series

Страница 1: ...LRP14AC LRP14HP 22 Wiring Diagrams LRP14AC LRP14HP 24 2021 Lennox Industries Inc Dallas Texas USA WARNING Improper installation adjustment alteration service or maintenance can cause property damage p...

Страница 2: ...13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY GAS...

Страница 3: ...RY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49 2 39 2...

Страница 4: ...1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 330 3 76...

Страница 5: ...76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bottom e...

Страница 6: ...Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 ADJUSTABLE PITCH ROOF CURB Usage A B C in mm in mm in mm 24 30 36 42 7 8 1089 13 7 8 352 16 7 8 429 42 48 60 51 3 8 1305 19 1 2 495 19 1 2 495 NOTE Roof dec...

Страница 7: ...arate request for inspection by the carrier s agent should be made in writing Location Use the following guidelines to select a suitable location for these units 1 Unit is designed for outdoor install...

Страница 8: ...t condenser air discharge outlet combustion air inlet or vent outlet Clearance to Combustibles Clearance for Service Access Front of unit 0 in 24 in Back of unit 0 in 0 in Left side 0 in 24 in Right s...

Страница 9: ...lated Vent Hood Installation The unit is shipped with the vent hood inside the control compartment Locate the vent hood and attach to side of utility panel with screws provided in the instruction bag...

Страница 10: ...SI Z223 1 latest edition or CAN CGA B149 1 2 Canadian Installation Codes to correct improper operation of common venting system Duct System The duct system should be designed and sized according to th...

Страница 11: ...ly upstream of the gas supply connection to the furnace Gas Connection The gas supply line is routed through the gas entry location on the side of the unit see Figure 4 A grommet is provided in the in...

Страница 12: ...adian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C minimum Run the 208 or 230 volt 60 hertz electric power supply...

Страница 13: ...uld be used to connect the thermostat to the unit Heating Start Up For Your Safety Read Before Lighting Furnace is equipped with a direct ignition control Do not attempt to manually light the burners...

Страница 14: ...he gas can be obtained from the local utility BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution For example by actual measurement it takes 38 seconds for the hand on...

Страница 15: ...inuous Fan With the proper thermostat and sub base continuous blower operation is possible by closing the R to G circuit Cooling blower delay is also functional in this mode 5 To change orifice a Remo...

Страница 16: ...dequate airflow occurs This closes the main gas valve Pressure Switch If the combustion air blower should fail the pressure switch prevents the spark electrode and gas valve from being energized Maint...

Страница 17: ...rder they were removed in Steps 1 through 3 10 When replacing the flue collector box be careful so as not to tear the adjoining insulation 11 Assure that all joints on the vent side of the combustion...

Страница 18: ...Page 18 Figure 8 Wiring Diagram Single Phase CT Wiring Diagram LRP14GE...

Страница 19: ...unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 7 1 Disconnect the power and open the main co...

Страница 20: ...from normal heating operation to defrost mode and back During the compressor cycle call for defrost the control accumulates compressor run time at 30 60 90 minute field adjustable intervals If the def...

Страница 21: ...pressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compressor is o...

Страница 22: ...16 3 5 Ton 22 4 Ton 22 5 Ton 5 Based on outdoor ambient temperature of 82 F and indoor entering air of 80 F db 67 F wb Table 8 Heat Pump Cooling System Performance Values Model Liquid Subcooling 2 2 T...

Страница 23: ...432 457 483 36 250 275 301 326 336 351 375 399 423 446 470 493 42 248 271 293 316 325 339 362 385 411 436 462 487 48 265 286 308 329 338 352 376 400 427 455 482 509 60 256 276 296 316 324 340 365 386...

Страница 24: ...WHT GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE...

Страница 25: ...will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has al...

Отзывы: