Page 22

System Performance

This equipment is a self-contained, factory optimized 

refrigerant system, and should not require adjustments to 

system charge when properly installed. If unit performance 

is questioned, perform the following checks.

Ensure unit is installed per manufacturer’s instructions 

and  that  line  voltage  and  air  flow  is  correct.  Refer  to 

the following tables for proper performance value. The 

indoor metering device varies by model; when checking 

performance of a unit using an orifice for metering, refer to 

the suction superheat value to judge performance. When 

checking performance of a unit that uses an expansion 

valve for metering, refer to the subcooling value to judge 

system performance. 

If the measured performance value varies from table value 

allowance, check internal seals, service panels and duct 

work for air leaks, as well as restrictions and blower speed 

settings. If unit performance remains questionable, remove 

system charge, evacuate to 500 microns, and weigh in 

refrigerant to nameplate charge. It is critical that the exact 

charge is re-installed. Failure to comply will compromise 

system performance. 

If unit performance is still questionable, check for 

refrigerant related problems, such as blocked coil or 

circuits, malfunctioning metering device or other system 

components.

Model 

Suction 

Sup/- 3°

Liquid 

Subc/- 2°

2 Ton

13

2.5 Ton

16

3 Ton

14

3.5 Ton

14

4 Ton

16

5 Ton

17

Based on outdoor ambient temperature of 82°F, and indoor 

entering air of 80°F db, 67°F wb.

Table 7. Air Conditioner Unit Cooling System 

Performance Values

Model 

Suction 

Sup/- 3°

Liquid Subcooling 

+/- 2°

2 Ton

18

2.5 Ton

16

3 Ton

16

3.5 Ton

22

4 Ton

22

5 Ton

5

Based on outdoor ambient temperature of 82°F, and indoor 

entering air of 80°F db, 67°F wb.

Table 8. Heat Pump Cooling System Performance 

Values

Model

Liquid Subc/- 2°

2 Ton

25

2.5 Ton

15

3 Ton

28

3.5 Ton

20

4 Ton

35

5 Ton

28

Based on outdoor ambient temperature of 47°F, and indoor 

entering air of 70°F db.

Table 9. Heat Pump Heating System Performance 

Values

Maintenance – LRP14AC/LRP14HP

Before performing maintenance operations on the 

system, shut off all electrical power to the unit. Turn off 

accessory heater power switch if applicable. Electrical 

shock could cause personal injury or death.

WARNING

Periodic inspection and maintenance normally consists of 

changing or cleaning the filters and cleaning the evaporator 

coil. On occasion, other components may also require 

cleaning.

Filters

Filters are not supplied with the unit. Inspect once a month. 

Replace disposable or clean permanent type as necessary. 

Do not replace permanent type with disposable.

Motors

Indoor and outdoor fan and vent motors are permanently 

lubricated and require no maintenance.

Indoor fans are equipped with a permanent magnet 

constant torque motor. These motors remain energized and 

are controlled by 24V signals. For high static applications, 

use Tap 3 for cooling speed and Tap 5 for heating speed.

Evaporator Coil

Dirt and debris should not be allowed to accumulate on 

the evaporator coil surface or other parts in the air circuit. 

Cleaning should be as often as necessary to keep coil 

clean. Use a brush, vacuum cleaner attachment, or other 

suitable means. If water is used to clean the coil, be sure 

the power to unit is shut off prior to cleaning. 

Care should 

be used when cleaning the coil so that the coil fins are 

not damaged.
Do not permit the hot condenser air discharge to be 

obstructed by overhanging structures or shrubs.

Содержание LRP14AC Series

Страница 1: ...LRP14AC LRP14HP 22 Wiring Diagrams LRP14AC LRP14HP 24 2021 Lennox Industries Inc Dallas Texas USA WARNING Improper installation adjustment alteration service or maintenance can cause property damage p...

Страница 2: ...13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY GAS...

Страница 3: ...RY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49 2 39 2...

Страница 4: ...1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 330 3 76...

Страница 5: ...76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bottom e...

Страница 6: ...Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 ADJUSTABLE PITCH ROOF CURB Usage A B C in mm in mm in mm 24 30 36 42 7 8 1089 13 7 8 352 16 7 8 429 42 48 60 51 3 8 1305 19 1 2 495 19 1 2 495 NOTE Roof dec...

Страница 7: ...arate request for inspection by the carrier s agent should be made in writing Location Use the following guidelines to select a suitable location for these units 1 Unit is designed for outdoor install...

Страница 8: ...t condenser air discharge outlet combustion air inlet or vent outlet Clearance to Combustibles Clearance for Service Access Front of unit 0 in 24 in Back of unit 0 in 0 in Left side 0 in 24 in Right s...

Страница 9: ...lated Vent Hood Installation The unit is shipped with the vent hood inside the control compartment Locate the vent hood and attach to side of utility panel with screws provided in the instruction bag...

Страница 10: ...SI Z223 1 latest edition or CAN CGA B149 1 2 Canadian Installation Codes to correct improper operation of common venting system Duct System The duct system should be designed and sized according to th...

Страница 11: ...ly upstream of the gas supply connection to the furnace Gas Connection The gas supply line is routed through the gas entry location on the side of the unit see Figure 4 A grommet is provided in the in...

Страница 12: ...adian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C minimum Run the 208 or 230 volt 60 hertz electric power supply...

Страница 13: ...uld be used to connect the thermostat to the unit Heating Start Up For Your Safety Read Before Lighting Furnace is equipped with a direct ignition control Do not attempt to manually light the burners...

Страница 14: ...he gas can be obtained from the local utility BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution For example by actual measurement it takes 38 seconds for the hand on...

Страница 15: ...inuous Fan With the proper thermostat and sub base continuous blower operation is possible by closing the R to G circuit Cooling blower delay is also functional in this mode 5 To change orifice a Remo...

Страница 16: ...dequate airflow occurs This closes the main gas valve Pressure Switch If the combustion air blower should fail the pressure switch prevents the spark electrode and gas valve from being energized Maint...

Страница 17: ...rder they were removed in Steps 1 through 3 10 When replacing the flue collector box be careful so as not to tear the adjoining insulation 11 Assure that all joints on the vent side of the combustion...

Страница 18: ...Page 18 Figure 8 Wiring Diagram Single Phase CT Wiring Diagram LRP14GE...

Страница 19: ...unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 7 1 Disconnect the power and open the main co...

Страница 20: ...from normal heating operation to defrost mode and back During the compressor cycle call for defrost the control accumulates compressor run time at 30 60 90 minute field adjustable intervals If the def...

Страница 21: ...pressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compressor is o...

Страница 22: ...16 3 5 Ton 22 4 Ton 22 5 Ton 5 Based on outdoor ambient temperature of 82 F and indoor entering air of 80 F db 67 F wb Table 8 Heat Pump Cooling System Performance Values Model Liquid Subcooling 2 2 T...

Страница 23: ...432 457 483 36 250 275 301 326 336 351 375 399 423 446 470 493 42 248 271 293 316 325 339 362 385 411 436 462 487 48 265 286 308 329 338 352 376 400 427 455 482 509 60 256 276 296 316 324 340 365 386...

Страница 24: ...WHT GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE...

Страница 25: ...will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has al...

Отзывы: