background image

Page 10

If an existing gas furnace is being removed from a 

common venting system when this packaged unit is 

installed, then read and follow the instructions in the 

“Removal of Unit from Common Venting System” section 

that follows. Otherwise, you may skip this section.

NOTE:

Removal of Unit from Common Venting System

When an existing furnace is removed from a common 

venting system serving other appliances, the venting 

system is likely to be too large to properly vent the 

remaining attached appliances. The following test 

should be conducted with each appliance while the other 

appliances connected to the common venting system are 

not in operation.

1.  Seal any unused openings in the common venting 

system.

2.  Visually inspect the venting system for proper size and 

horizontal pitch and determine there is no blockage 

or restriction, leakage, corrosion, or other deficiencies 

which could cause an unsafe condition.

3.  Insofar as is practical, close all building doors and 

windows between the space in which the appliances 

remaining connected to the common venting system 

are located and other spaces in the building. Turn on 

clothes dryers and any appliance not connected to the 

common venting system. Turn on exhaust fans, such 

as range hoods and bathroom exhausts, so they will 

operate at maximum speed. Do not operate a summer 

exhaust fan. Close fireplace dampers.

4.  Following the lighting instructions, place the unit being 

inspected in operation. Adjust the thermostat so the 

appliance will operate continuously.

5.  Test for spillage at the draft control relief opening after 

5 minutes of main burner operation. Use the flame of 

a match or candle.

6.  Follow the preceding steps for each appliance 

connected to the common venting system.

7.  After it has been determined that each appliance 

remaining connected to the common venting system 

properly vents when tested as outlined above, return 

doors,  windows,  exhaust  fans,  fireplace  dampers, 

and any other fuel burning appliance to their previous 

condition of use.

8.  If improper venting is observed during any of the 

above tests, the common venting system must be 

corrected. See National Fuel Gas Code, ANSI Z223.1 

(latest edition) or CAN/CGA B149.1 & .2 Canadian 

Installation Codes to correct improper operation of 

common venting system. 

Duct System

The duct system should be designed and sized according 

to the methods in the Air Conditioning Contractors of 

America (ACCA) manual that is most appropriate to the 

installation application.

A closed return air duct system shall be used. This shall 

not preclude use of economizers or outdoor fresh air 

intake. It is recommended that supply and return air duct 

connections at the unit be made with flexible joints.

The supply and return air duct systems should be designed 

for the CFM and static requirements of the job. They 

should not be sized by matching the dimensions of the 

duct connections on the unit. 

The  unit  is  shipped  ready  for  horizontal  flow  (side  duct 

connections)  or  downflow  (bottom  duct  connections). All 

units are equipped with a drain pan overflow switch that is 

installed and wired at the factory. Duct attachment screws 

are intended to go into the duct panel flanges. Duct to unit 

connections must be sealed and weather proofed.

For horizontal duct systems:

1.  Remove the duct covers on side of the unit. They can 

be discarded.

2.  Install the duct system to the unit.

For downflow duct systems:

1.  Remove the duct covers on side of the unit. Keep the 

screws and the covers as they will be re-installed later.

2. 

Remove the downflow duct covers located inside unit. 

Remove the four screws securing each cover. Remove 

the covers from the unit. They can be discarded.

3.  Remove screws located between the supply and 

return air openings that attach the blower deck to the 

base pan. These screws can interfere with bottom duct 

connections or roof curb seals. Discard these screws.

4.  Install the duct system to the unit.
5.  Re-install the duct covers removed in Step 1.

Filters

Air filters are not supplied with the unit. A field-provided air 

filter must always be installed ahead of the evaporator coil 

and must be cleaned or replaced if necessary. Dirty filters 

will reduce the airflow of the unit. 

An  optional  filter  rack  kit  may  be  purchased  separately 

for installation inside the unit’s coil compartment. Air filter 

sizes are shown in Table 2 for use with filter rack kit.

The filter rack must be installed prior to installation of 

the unit in applications where access to the rear panel 

is limited.

NOTE:

Содержание LRP14AC Series

Страница 1: ...LRP14AC LRP14HP 22 Wiring Diagrams LRP14AC LRP14HP 24 2021 Lennox Industries Inc Dallas Texas USA WARNING Improper installation adjustment alteration service or maintenance can cause property damage p...

Страница 2: ...13 44 13 44 14 32 16 06 6 20 40 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS 11 49 2 33 47 66 1 98 16 77 2 48 14 02 47 66 POWER ENTRY GAS...

Страница 3: ...RY 7 8 DIA KNOCKOUT GAS SUPPLY 44 89 21 63 13 21 TYPICAL DRAIN LOCATION CONDENSATE DRAIN 3 4 NPT 5 75 3 55 4 12 TYPICAL VENT HOOD SIDE VIEWS TOP VIEW POWER ENTRY GAS ENTRY RETURN AIR 2 11 19 49 2 39 2...

Страница 4: ...1127 44 3 8 1127 16 7 8 429 13 7 8 352 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 4 19 1 25 5 1 2 140 5 3 4 146 11 1 2 287 17 1 4 438 1 3 8 35 3 3 4 95 13 330 3 76...

Страница 5: ...76 x 330 mm 52 7 8 1343 44 3 8 1127 19 1 2 380 11 1 2 287 19 1 2 380 2 1 8 54 11 1 2 287 SUPPLY OPENING RETURN OPENING 8 203 14 356 18 457 24 610 3 3 4 95 22 7 8 581 7 178 3 4 19 1 25 NOTE If bottom e...

Страница 6: ...Minimum Height 4 102 UNIT BASE RAIL CLIPS 4 ADJUSTABLE PITCH ROOF CURB Usage A B C in mm in mm in mm 24 30 36 42 7 8 1089 13 7 8 352 16 7 8 429 42 48 60 51 3 8 1305 19 1 2 495 19 1 2 495 NOTE Roof dec...

Страница 7: ...arate request for inspection by the carrier s agent should be made in writing Location Use the following guidelines to select a suitable location for these units 1 Unit is designed for outdoor install...

Страница 8: ...t condenser air discharge outlet combustion air inlet or vent outlet Clearance to Combustibles Clearance for Service Access Front of unit 0 in 24 in Back of unit 0 in 0 in Left side 0 in 24 in Right s...

Страница 9: ...lated Vent Hood Installation The unit is shipped with the vent hood inside the control compartment Locate the vent hood and attach to side of utility panel with screws provided in the instruction bag...

Страница 10: ...SI Z223 1 latest edition or CAN CGA B149 1 2 Canadian Installation Codes to correct improper operation of common venting system Duct System The duct system should be designed and sized according to th...

Страница 11: ...ly upstream of the gas supply connection to the furnace Gas Connection The gas supply line is routed through the gas entry location on the side of the unit see Figure 4 A grommet is provided in the in...

Страница 12: ...adian Electrical Code Part 1 CSA C22 1 latest edition or local codes where they prevail Use wiring with a temperature limitation of 75 C minimum Run the 208 or 230 volt 60 hertz electric power supply...

Страница 13: ...uld be used to connect the thermostat to the unit Heating Start Up For Your Safety Read Before Lighting Furnace is equipped with a direct ignition control Do not attempt to manually light the burners...

Страница 14: ...he gas can be obtained from the local utility BTU HR Input Cubic Feet per Revolution x 3600 x Heating Value Seconds per Revolution For example by actual measurement it takes 38 seconds for the hand on...

Страница 15: ...inuous Fan With the proper thermostat and sub base continuous blower operation is possible by closing the R to G circuit Cooling blower delay is also functional in this mode 5 To change orifice a Remo...

Страница 16: ...dequate airflow occurs This closes the main gas valve Pressure Switch If the combustion air blower should fail the pressure switch prevents the spark electrode and gas valve from being energized Maint...

Страница 17: ...rder they were removed in Steps 1 through 3 10 When replacing the flue collector box be careful so as not to tear the adjoining insulation 11 Assure that all joints on the vent side of the combustion...

Страница 18: ...Page 18 Figure 8 Wiring Diagram Single Phase CT Wiring Diagram LRP14GE...

Страница 19: ...unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 7 1 Disconnect the power and open the main co...

Страница 20: ...from normal heating operation to defrost mode and back During the compressor cycle call for defrost the control accumulates compressor run time at 30 60 90 minute field adjustable intervals If the def...

Страница 21: ...pressor delay jumper is removed NOTE The 30 second off cycle is not functional when jumpering the TEST pins Time Delay The defrost control includes a compressor timer which ensures the compressor is o...

Страница 22: ...16 3 5 Ton 22 4 Ton 22 5 Ton 5 Based on outdoor ambient temperature of 82 F and indoor entering air of 80 F db 67 F wb Table 8 Heat Pump Cooling System Performance Values Model Liquid Subcooling 2 2 T...

Страница 23: ...432 457 483 36 250 275 301 326 336 351 375 399 423 446 470 493 42 248 271 293 316 325 339 362 385 411 436 462 487 48 265 286 308 329 338 352 376 400 427 455 482 509 60 256 276 296 316 324 340 365 386...

Страница 24: ...WHT GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE...

Страница 25: ...will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has al...

Отзывы: