1
Introduction
This document provides an installation guide and user operation manual for the E-Flex relay panel. The
E-Flex relay panel is designed for 120-277V AC, 47-63 Hz installations providing controlled switching of
four or eight zones as well 0-10V dimming. Inputs for occupancy and daylight sensors provide for
standalone energy management.
The following E-Flex relay panel models are available:
EFRP-04, 4 relays and 0-10V dimming
EFRP-08, 8 relays and 0-10V dimming
Features and Specification
Surface mount enclosure
4 or 8 mechanically latching relays with the following ratings:
o
Resistive: 50A @ 277VAC, 20A 347VAC
o
Tungsten: 20A @ 240 VAC, 277VAC
o
Standard Ballast: 20A @ 120VAC, 277VAC, 347VAC
Electronic Ballast: 16A @ 120VAC, 277VAC
4 or 8, 0-10V outputs with current sink of 80mA.
Inte24V DC power supply to provide power for sensors and E-FlexNet devices.
Dry contact closure inputs for UL924, timeclock, fire alarm, and demand response.
4 banks of inputs for occupancy, daylight, and contact closure.
19 presets plus OFF for up to eight zones.
DMX512 input with RDM (Remote Device Management) support as well as Impress link mode to
support SDE impress remote stations.
Software Version
The features and user interface described in this manual are supported with E-Flex software versions
V1.05 and higher.