31
E-Flex User Manual, Rev. 1.30
Device ID
Set the Device ID for use with FlexNet as well as RDM info. Each E-Flex relay panel must have a unique ID
for FlexNet and should have a unique ID when more than one panel is used with DMX/RDM.
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Down
button twice to display the
device id
menu.
Press
Enter
to display the current device id value.
Use the
Up
and
Down
buttons to select an ID from 1-100.
Press
Store button
to record the new setting.
Press
Menu
to exit. See Menu navigation.
DASC – Daylight Scaler, Primary/Secondary Daylight Zone Adjustment
Use this menu to adjust the secondary daylight zone(s) when using one photocell to control more than
one daylight zone. Typically the primary daylight zone is closest to a window; secondary daylight zones
are farther away so will require more light from the luminaire. This menu lets you reduce the effect of
the daylight sensor (photocell) on a zone by scaling the dimming from the photocell.
Press
Enter
at the
control
menu, the
Clear memory
menu is displayed.
Press the
Down
button to display the
DAsc
menu item.
Press
Enter
to display the
zone select
entry control.
Use the
Up
and
Down
buttons to select a zone to adjust.
Press
Enter
to display the current adjustment level for the zone. Use the
Up
and
Down
buttons to set the scaling from 0-100. At 0 the daylight sensor has
no effect; at 100 the daylight sensor has full control. The default is 100%.
Press
Store button
to record the new setting.
Press
Menu
to exit. See Menu navigation.