10
E-Flex User Manual, Rev. 1.30
0-10V Outputs
#20-12 AWG wires, strip length – ¼ in., torque – 3.5 lbs.
Sinking only outputs.
Connect only to NEC Class 2 circuits.
Limit distance run for analog control wiring from controller to last driver. Limiting to a voltage
drop of .3V maximum will help ensure meeting IEC 60929 Annex E standard for minimum light
level at 1V.
Note: additional 0-10V outputs for outputs 5 thru 8 as shown in the low voltage side diagram on page 8.
DMX Input
#24-12 AWG wires, strip length – ¼ in., torque – 1.7 lbs
E-FlexNet
#24-12 AWG wires, strip length – ¼ in., torque – 3.5 lbs