18
E-Flex User Manual, Rev. 1.30
Contact Closure Inputs
Navigate to cciX menu
Press
Menu,
inpX
menu is displayed.
Press
Enter
, the
occX
menu is displayed.
Press the
Up
button twice to scroll to the
cciX
menu.
Note: The user can press the
Input
button at this time to switch to an CCI input on a different input bank.
The menu will advance from cci1 to cci2, thru to cci4.
Set Input Polarity
Press
Enter
at the
cciX
menu, the
Polarity
list control is displayed.
Press
Enter
for the polarity options list. The current programmed option will
be displayed first.
Use the
Up
and
Down
buttons to display the available options:
NO – normally open (default)
NC – normally closed
Press
Sel
to choose the displayed option. The apostrophe LED will be lit for the current selected option.
Press
Store
button to record the new setting.
Set Contact Closure Mode
Press
Enter
at the
cciX
menu, the
Polarity list control
is displayed.
Press the
Up
button to scroll to the
options
list control.
Press
Enter
for options list. The current programmed option will be displayed first.
Use the
Up
and
Down
buttons to display the available options:
Opt1
– momentary, toggle assigned zones between preset and off.
Opt2*
- momentary, turn on assigned zones to preset.
Opt3
- maintained, toggle assigned zones between preset and off.
Opt4
- maintained, closure turns on assigned zones to preset, open to off. (default)
Press
Sel
to choose the displayed option. The apostrophe LED will be lit for the current programmed
option. Press
Store button
to record the new setting.
*Only in this mode can the response preset can be set to off