User Manual of EL6-CAN AC Servo
www.leadshine.com
45
Set up the torque limit at emergency stop
When setup value is 0, the torque limit for normal operation is applied.
Compared with the maximum torque 6072, the actual torque limit value is smaller one.
Pr5.12
Name
Over-load level setup
Mode
F
Range
0~115
Unit
%
Default
0
Index
2512h
You can set up over-load level. The overload level becomes 115% by setting up this value to 0.
Use this with 0 setup in normal operation, set up other value only when you need to low this over-load
level.
The setup value of this parameter is limited by 115% of the motor rating.
Pr5.13
Name
Over-speed level setup
Mode
F
Range
0~10000
Unit
RPM
Default
0
Index
2513h
If the motor speed exceeds this setup value, Err1A.0 [over-speed protect] occurs.
The over-speed level becomes 1.2 times of the motor max, speed by setting up this to 0.
Pr5.20
Name
Position setup unit select
Mode
F
Range
0~2
Unit
—
Default
2
Index
2520h
Specify the unit to determine the range of positioning complete and excessive positional deviation
Setup value
unit
0
Encoder unit
1
Command unit
2
Standard 2500-line unit
Pr5.21
Name
Selection of torque limit
Mode
F
Range
0~2
Unit
—
Default
0
Index
2521h
Set up the torque limiting method;
Setup value
Positive limit value
Negative limit value
0
Pr0.13
Pr0.13
1
Pr0.13
Pr5.22
2
60E0
60E1
Compared with the maximum torque 6072, the actual torque limit value is smaller one
Pr5.22
Name
2nd torque limit
Mode
F
Range
0~500
Unit
%
Default
300
Index
2522h
Set up the 2
nd
limit value of the motor torque output
The value of the parameter is limited to the maximum torque of the applicable motor.
Compared with the maximum torque 6072, the actual torque limit value is smaller one
Pr5.28
Name
LED initial status
Mode
F
Range
0~42
Unit
—
Default
34
Index
2528h