User Manual of EL6-CAN AC Servo
www.leadshine.com
44
Pr4.43
Name
E-stop function
Mode
F
Range
0~1
Unit
-
Default
0
Index
2443h
0
:
When E-STOP is effective, the servo will forced to STOP and servo-disabled, and alarm showing
(
Err570
)
.
1
:
When E-STOP is effective, the servo will forced to STOP and keep in servo-enable, no alarm showing.
4.2.6
【
Class 5
】
Extended Setup
Pr5.04
Name
Over-travel inhibit input setup
Mode
F
Range
0~2
Unit —
Default
0
Index
2504h
set to 1, no effect on homing mode.
Setup value Details
0
positive and negative limit effective, no alarm output
1
positive and negative limit effective invalid
2
positive and negative limit effective, alarm Err26.0
In homing mode, POT/NOT invalid Settings please set the object dictionary 5012-04 bit0=1
Pr5.06
Name
Stop mode
Mode
F
Range
0~1
Unit
—
Default
0
Index
2506h
Specify the status during deceleration and after stop, after servo-off.
Setup value
Details
0
Disabled when disable signal effective and speed reduce to Pr4.39
1
Disabled when disable signal effective, free-run to stop
Pr5.08
Name
LV trip selection at main power OFF
Mode
F
Range
0~1
Unit
—
Default
1
Index
2508h
You can select whether or not to activate Err0d.0 (main power under-voltage protection)function while the
main shutoff continues for the setup of Pr5.09(The main power-OFF detection time).
Setup value
Action of main power low voltage protection
0
When the main power is shut off during Servo-On,Err0d.0 will not be triggered and the
drive turns to Servo-OFF. The drive returns to Servo-On again after the main power
resumption.
1
When the main power is shut off during Servo-On, the drive will trip due to Err0d.0
Caution:
Err0d.0(main power under-voltage protection) is trigged when setup of Pr5.09 is long and P-N
voltage of the main converter falls below the specified value before detecting the main power shutoff ,
regardless of the Pr5.08 setup.
Pr5.09
Name
The main power-OFF detection
time
Mode
F
Range
70~2000
Unit
1ms
Default
70
Index
2509h
You can set up the time to detect the shutoff while the main power is kept shut off continuously. The
main power off detection is invalid when you set up this to 2000.
Pr5.11
Name
Torque setup for emergency stop
Mode
F
Range
0~500
Unit
%
Default
0
Index
2511h