Installation and maintenance manual lba12
24
o
"USER PARAMETERS" - Settings for the program:
The "USER PARAMETERS" functions provides access to the list of user settings that can be modified in order to adjust the barrier.
Some of these settings can be accessed only via the "ADMIN" user.
Here is the list of default settings:
Setting
Description
Unit
OP
ADMIN
T_manoeuvre
Time beyond which the barrier goes into
fault if neither of the two end-of-travel
sensors has been detected. (default: 30s)
s
●
●
FAT
Activation of automatic closing after time
delay
(TRUE: activated; FALSE: deactivated).
●
●
FAP
Activation of automatic closing after
passage on the safety loop
(TRUE: activated; FALSE: deactivated).
●
●
T_FAT
Waiting time before automatic closing after
time delay (if activated) (default: 15s)
s
●
●
T_FAP
Waiting time before automatic closing after
passage (if activated) (default: 0s)
s
●
●
T_Detection_FAP
Minimum duration for detection on the
magnetic loop so that the closing after
passage is activated (default: 0.5s)
s
●
●
T_PVT
Duration of the small speed timed for
closing (case with irreversible barriers)
(default: 1s)
s
●
●
Presign_OUV
Duration of the pre-signalling before the
opening of the barrier. (default: 0s)
s
●
●
Presign_FERM
Duration of the pre-signalling before the
closing of the barrier. (default: 0s)
s
●
●
Clignotement_feux
Activation of blinking lights on arm
(TRUE: activated; FALSE: deactivated).
●
●
Mode_1_BP
Activation of the "1 BP" control mode which
makes is possible to control the barrier with
a single control: the opening control then
becomes a closing control when the barrier
is open
(TRUE: activated; FALSE: deactivated).
●
●
Mode_homme_mort
Activation of the "dead man" control mode:
the closing control has to be maintained
until the end of closing otherwise the barrier
will open again automatically
(TRUE: activated; FALSE: deactivated).
●
●
Mode_capteurs_NC
Configuring of the end-of-travel sensors as
normally closed (NC) instead of normally
open (NO)
(TRUE: NC; FALSE: NO).
●
●
Activation_deverr
Option to be activated when the barrier is
provided with a mechanical locking member
(excluding electromagnetic suction cup) so
that the barrier closes very slightly before
each opening in order to release the locking
(TRUE: activated; FALSE: deactivated).
●
●
PWM_verrou
Activation of the PWM function on the
locking output (Q3) in order to consume
less
(TRUE: activated; FALSE: deactivated).
●
●
Param_Vit_1
Opening speed of the barrier.
Hz
●
●
Param_Vit_2
Closing speed of the barrier.
Hz
●
●
Param_Vit_3
Slowdown speed (holding torque) in
opening
Hz
●
●
Param_Vit_4
Slowdown speed (holding torque) in closing
Hz
●
●
Param_Vit_5
Acceleration ramp of the barrier in opening.
Hz/s
●
●
Param_Vit_6
Acceleration ramp of the barrier in closing.
Hz/s
●
●
Param_Vit_7
Deceleration ramp of the barrier in opening.
Hz/s
●
●
Param_Vit_8
Deceleration ramp of the barrier in closing.
Hz/s
●
●
Param_Vit_9
Opening speed of the barrier during
automatic rehinging.
Hz
●
●
Regondage_auto
Activation of the automatic rehinging
function (LBA63PG)
(TRUE: activated; FALSE: deactivated).
●