Installation and maintenance manual lba12
20
•
Information" screen (default screen):
This display is the default screen, it indicates useful information for the installer:
-
Frequency of the motor (in Hz):
this corresponds to the frequency of the current injected
into the motor. This frequency is positive in the opening direction and negative in the closing
direction.
-
Number of cycles carried out:
the number of cycles carried out by the barrier corresponds
to the number of openings
-
Current status of the barrier:
this message indicates the status of the barrier (see "§3.1.
Status messages of the barrier")
Note: This display will return automatically if no button is pressed for 60s
•
“Advanced settings” screens (press "ESC" for 2s):
To access the advanced settings screens, keep the "ESC" pressed for 2s. You will then see the first screen for advanced settings,
simply click one of the two arrows to go to the second screen.
These displays indicate the advanced settings:
-
Number of cycles of the barrier:
this number of cycles corresponds to the number of
openings carried out by the barrier.
-
Number of unhingings that the barrier was subjected to:
this number indicates the
number of unhingings that the barrier has been subjected to.
-
Programme of the barrier:
this shows the programme number as well as its version. This
information is useful when troubleshooting.
-
Direct voltage of the bus (in V):
this voltage allows you to check that there is no fault on
the direct bus of the variator. This voltage must be about 300V ± 20V.
-
Temperature of the IGBT module of the variator (in °C):
this temperature makes it
possible to verify that there is no overheating on the IGBT module of the frequency variator.
This temperature must be less than
-
IP address of the barrier:
This is the IP address of the barrier for the Modbus
communication.
Note: The screen display automatically returns to the "Information" screen after 60s if no button is pressed.
•
Status of the inputs/outputs" screen (hold "ENTER" for 2s):
To access the screen for viewing the status of the inputs/outputs, press and hold the « ENTER » button for 2s.
The screen shows the statuses of the 4 different input/output types (0: inactive; 1: active):
-
Analogue/digital inputs (AI):
AI1 to AI4
-
Digital inputs (I):
I1 to I8
-
Transistor outputs (Q):
Q1 to Q6
-
Relay outputs (QR):
QR1 to QR6
====Informations====
Fr: -7 Hz
Cycles: 125
BARRIER CLOSED
====Advanced 1/2====
Cycles: 125
Unhingings: 37
Prog: PROG009714 v1
====Advanced 2/2====
U : 304 Vdc
Temp : 49 C
IP : 192.168.0.100
===Inputs-Outputs===
AI:0101 I:01101100
Q:101000 QR :001101