Proline Kryomats
126
Technical data
11/13/2018
Mains connection data
Proline Kryomat air-cooled
Mains connection data
RP 3050 C
RP 4050 C
RP 3090 C
RP 4090 C
400 V +8/-10 %; 3/N/PE~50 Hz
X
X
X
X
208 V ±8 %; 3/PE~60 Hz
X
X
X
X
200 V ±10 %; 3/PE~50/60 Hz
X
X
X
X
Proline Kryomat water-cooled
Mains connection data
RP 3050 CW
RP 4050 CW
RP 3090 CW
RP 4090 CW
400 V +8/-10 %; 3/N/PE~50 Hz
X
X
X
X
208 V ±8 %; 3/PE~60 Hz
X
---
X
X
200 V ±10 %; 3/PE~50/60 Hz
X
X
---
X
Technical modifications reserved.
Refrigerant and Filling quantity
The cooling thermostat contains fluorinated greenhouse gases.
Unit
RP 3050 C
RP 3050 CW
RP 4050 C
RP 4050 CW
Refrigerant
---
R-404A
R-404A
R-404A
R-404A
maximum filling quantity
kg
1.5
1.5
1.5
1.5
GWP
(100a)
*
---
3922
3922
3922
3922
CO
2
equivalent
t
5.9
5.9
5.9
5.9
Devices with two compressors
Unit
RP 3090 C
RP 3090 CW
RP 4090 C
RP 4090 CW
Refrigerant 1
---
R-404A
R-404A
R-404A
R-404A
maximum filling quantity
kg
1.5
1.5
1.5
1.5
GWP
(100a)
*
---
3922
3922
3922
3922
CO
2
equivalent
t
5.9
5.9
5.9
5.9
Refrigerant 2
---
R-508B
R-508B
R-508B
R-508B
maximum filling quantity
kg
0.73
0.73
0.73
0.73
GWP
(100a)
*
---
13210
13210
13210
13210
CO
2
equivalent
t
9.6
9.6
9.6
9.6
Global Warming Potential (GWP),
Comparison CO
2
= 1,0
* Time span 100 years
– according to IPCC IV
Содержание RP 3050 C
Страница 1: ...2SHUDWLQJ LQVWUXFWLRQV 352 1 U RPDWV RZ WHPSHUDWXUH 7KHUPRVWDWV 53 53 53 53 53 53 53 53 ...
Страница 2: ......
Страница 4: ......
Страница 40: ...Proline Kryomats 40 Starting up YAUE0007 10 2 2018 7 Starting up ...
Страница 41: ...Proline Kryomats YAUE0007 10 2 2018 Starting up 41 ...
Страница 132: ...Proline Kryomats 132 YAUE0007 10 2 2018 ...
Страница 134: ......
Страница 135: ......