In industrial installations, the current leakage can happen to earth because of
the following main reasons:
i)
Current leakage through phase to earth insulations
ii) Leakage of current through phase to earth leakage capacitance
Due to the high insulation resistance the leakage current magnitude remains
low in terms of milliamps or micro amps. Assuming that the phase-to-earth
insulation resistance in an LV network is just 1 Mega-ohm(*), then the leakage
current to earth will be (240V/1 Mega-ohm) 240 microamperes. But, generally
the phase-to-earth insulation resistance would be much higher than just
1Mega-ohm, normally a few tens or even hundreds of Mega-ohms. Thus, the
leakage current to earth will be a further fraction of the micro-ampere or even
nano-amperes. As human body’s sensible current is more than 1 milli-ampere,
this remains un-sensed by a human being coming in contact with the earthed
frame of an LV electrical installation.
Any leakage current above 300mA can result into fire in electric installations. In Industrial areas especially in mining
application the earth leakage protection becomes critical for the fire safety.
Omega Matrix Earth Leakage module has Earth leakage current monitoring range of 300mA to 30A. The EL module
communicates on CAN bus with the Matrix releases which can be set in Alarm, Trip or “Both”mode.
S
o
m
e
m
o
r
e
f
e
a
t
u
r
e
s
o
f
E
L
m
o
d
u
l
e
:
•
"NO" contact for external indications (24V DC/240V AC, 6A)
•
Standalone module
•
Dip switches for configuring pickup and delay settings
•
Self-diagnostic check for module healthiness check
*As per Indian Electricity rule, 1956, Rule No. 48(ii) For Medium & Low Voltage Installations, Voltage at a pressure of 500 V applied
between each live conductor and earth for a period of one minute, the insulation resistance of medium and low voltage installations shall
be at least 1 Mega ohm.
60
Matrix
Modules
POWER SUPPLY (PS) MODULE
PS module is used to power ON other supplementary modules of
OMEGA Matrix release family as well as to communicate on the
CAN bus through RJ45 shielded cable.
Note :
For VA burden details of modules & optimal usage of PS modules refer Matrix User’s manual
* For using Output 1, Output 2 should be loaded first
D
I
G
I
T
A
L
I
N
P
U
T
O
U
T
P
U
T
(
D
I
O
)
M
O
D
U
L
E
Matrix DIO module is provided with 4 digital inputs and 4 digital
outputs for the implementation of various Boolean logic
equations into the system.
Some features of DIO module
•
Up to 4 DIO modules can be looped together to one MATRIX
release
•
Dip switches on the Module facia for setting the node address
•
16 different logic equations can be assigned
•
Self-diagnostic test provision
C
o
n
t
a
c
t
R
a
t
i
n
g
s
I
n
p
u
t
c
o
n
t
a
c
t
s
24V DC or 240V AC
O
u
t
p
u
t
C
o
n
t
a
c
t
s
24V DC or 240V AC, 6A (resistive load)
TRIP CIRCUIT SUPERVISION (TCS) MODULE
TCS module of Matrix Releases continuously monitors the
healthiness of the shunt trip coil irrespective of the breaker
operational position. Protection can be set in both, trip or alarm
mode in the release unit.
•
Detects circuit breakage, contact degeneration in
connections, resistance increase in wires, contacts and coils of
the supervised shunt release
•
Complete range of rated voltage (24-415V) either AC or DC
•
Standalone module
•
Self-diagnostic test provision
125-300V
200mA @ 24V DC
650mA @ 24V DC
Input
Output 1*
Output 2
S
p
e
c
i
f
i
c
a
t
i
o
n
s
A
C
D
C
85-265V
-
-
Содержание OMEGA
Страница 2: ...Stabilise systems with technology ...
Страница 4: ...Change course quickly ...
Страница 6: ...Match performance with prudence ...
Страница 8: ...Adopt technological brilliance ...
Страница 10: ...Keep an eye on upkeep ...
Страница 26: ...Matrix Protection Control Units T UW M X4 5 ...
Страница 70: ...Accessories ...
Страница 84: ...Control Circuit Wiring ...
Страница 92: ...Mounting Termination ...
Страница 135: ...SP 50567 R5 ...