61
Matrix
Communication Protocols
Modbus:
Monitoring function:
Modbus Module is used for the Configuration,
1) Metering Data – Voltage, Current, Power, Energy,
Monitoring and Control of Matrix releases and
Power Factor, Online Module Status
its supplementary modules.
2) Status Data – Alarm & Trip Status, Digital Input
Output Module & Relay Module Status
It offers Client/Server communication in RTU mode.
3) Record Data – Trip Records, Event Records,
Maintenance Records
Configuration function:
1) Unit Settings
Control function:
2) System Settings
1) Commands for Set group Change, Restore Factory
3) Protection Settings Group 1
Defaults, Clear Maximum Demand
4) Protection Settings Group 2
2) Maximum Current value, Maximum Voltage Value
5) Module Settings
and Energy, Open and Close Circuit
3) Breaker, Maintenance Acknowledgement and
Earth Fault (EF) test
M-G C-G D+ D- V1 V2 V3 V0 AS+ AS-
DATA+
VS +
SHIELD
GND
DATA-
SIC Termination
COMMUNICATION LED
Blinks RED during communication data transfer
P
C
H
M
I
PS MODULE
Pre-wired Connections inside breaker
Shielded Co-axial 2 core Cable
CONVERTER
?
MODBUS
CONFIGURATOR
METERING MODULE
S
T
A
T
U
S
T
E
S
T
C
O
M
M
MODBUS
SELF-TEST SWITCH
For factory use only
STATUS LED
Blinks AMBER for 5s when Module is connected indicating self-test.
Blinks GREEN continuously to indicate healthy POWER ON.
Glows RED if unhealthy / self-test fails.
62
Matrix
Communication Protocols
Profibus:
Profibus Module supports PROFIBUS DP V0 slave protocol. This module communicates with PROFIBUS Class 1 and/or
Class 2 Master.
GSD file should be used/loaded in PROFIBUS master for understanding the device functions. Network termination
switch is provided at the rear end of the module. Thus this module can be used as end node in the network.
It communicates on baud-rates 9.6Kbps, 19.2Kbps, 45.45Kbps, 93.75Kbps, 187.5Kbps, 500Kbps, 1.5Mbps,
3Mbps, 6Mbps, 12Mbps. It automatically detects the baud-rate selected by PROFIBUS master for communication.
PROFIBUS module is used to monitor and configure critical status parameters of Matrix Release like Pick-up, Alarm
and Trip status.
PROFIBUS
M-G C-G D+ D- V1 V2 V3 V0 AS+ AS-
DATA+
SHIELD
DATA-
SIC Termination
P
R
O
F
I
B
U
S
M
A
S
T
E
R
o
r
P
L
C
PS MODULE
PROFIBUS CABLE
Pre-wired Connections inside breaker
Shielded Co-axial 2 core Cable
SELF-TEST SWITCH
For factory use only
STATUS LED
Blinks AMBER for 5s when Module is connected indicating self-test.
Blinks GREEN continuously to indicate healthy POWER ON.
Glows RED if unhealthy / self-test fails.
COMMUNICATION LED
Blinks RED during communication data transfer
S
T
A
T
U
S
T
E
S
T
C
O
M
M
?
PROFIBUS
CONFIGURATOR
METERING MODULE
PROFIBUS
CONFIGURATOR
METERING MODULE
Содержание OMEGA
Страница 2: ...Stabilise systems with technology ...
Страница 4: ...Change course quickly ...
Страница 6: ...Match performance with prudence ...
Страница 8: ...Adopt technological brilliance ...
Страница 10: ...Keep an eye on upkeep ...
Страница 26: ...Matrix Protection Control Units T UW M X4 5 ...
Страница 70: ...Accessories ...
Страница 84: ...Control Circuit Wiring ...
Страница 92: ...Mounting Termination ...
Страница 135: ...SP 50567 R5 ...