63
Matrix
Communication Protocols
Zigbee:
Our innovative Matrix releases are designed to let consultants & system designers help their customers & end-users
gain greater control of, and improve their everyday business & industrial processes by means of “ZigBee wireless
communication” capability.
UW-MTX3.5/3.5EC/4.5 provides Wireless Communication using ZigBee protocol formulated under IEEE 802.15.4
standard for Wireless Personal Area Network (WPANs). Zigbee operates in ISM radio bands of 2.4GHz.
The Communication range is 200m Line Of Sight (LOS) with over the air data rates upto 250 Kbps. Zigbee module is
used for Monitoring parameters of Matrix releases and its supplementary modules.
Monitoring function:
1) Metering Data – Voltage, Current, Power, Energy, Power Factor, Online Module Status
2) Status Data – Alarm & Trip Status, Digital Input Output Module & Relay Module Status
3) Record Data – Trip Records, Event Records, Maintenance Records
Note:
1) It is necessary to first switch on the Co-ordinator module and form a network. Co-ordinator Module can be
directly plugged in the PC USB port or USB cable can be used.
2) Power LED on Co-ordinator Module will glow GREEN when connected to the port. Network LED on Co-ordinator
module will glow GREEN when it forms a network.
3) Zigbee Module should be now inserted in the Matrix P&C unit .
ZIGBEE
M-G C-G D+ D- V1 V2 V3 V0 AS+ AS-
SIC Termination
PS MODULE
PC HMI
USB CABLE
(OPTIONAL)
POWER
LED
NETWORK
LED
ZIGBEE
CO-ORDINATOR
u
SELF-TEST SWITCH
For factory use only
u
STATUS LED
Blinks AMBER for 5s when Module is connected indicating self-test.
Blinks GREEN continuously to indicate healthy POWER ON.
Glows RED if unhealthy / self-test fails.
u
COMMUNICATION LED
Glows RED when not in network.
Blinks RED during communication data transfer
S
T
A
T
U
S
T
E
S
T
C
O
M
M
PROFIBUS
CONFIGURATOR
METERING MODULE
ZIGBEE
CONFIGURATOR
METERING MODULE
?
64
Smart Configurator
Smart Configurator:
UW-MTX3.5/3.5EC/4.5 has an optional Smart Configurator Module which is used for easy parameterisation of the
release. In large electrical installations, where many ACBs are in use; one can copy the release protection parameters
setting on smart card and then copy the parameters on various releases. Smart Configurator Module in MTX releases
with its ease of use can reduce the gestation period of electrical installation.
Smart Configurator works on the principle of RF interface at 106kbps between the module and the Smart Card.
The following operations can be performed on the Smart Card:
1) Write File: Copy files from the release to the card
2) Read File: Copy files from the card to the release
3) Delete File: Delete selected file from the card
4) Format Card: Delete all the files from the card and format it
CONFIGURATOR
M-G C-G D+ D- V1 V2 V3 V0 AS+ AS-
SIC Termination
PS MODULE
u
(Card goes inside the module partially. Check the Comm LED to see
whether the card is detected.)
INSERT CARD HERE
u
SELF-TEST SWITCH
For factory use only.
u
STATUS LED
Blinks AMBER for 5s when Module is connected indicating self-test.
Blinks GREEN continuously to indicate healthy POWER ON.
Glows RED if unhealthy / self-test fails.
u
COMMUNICATION LED
Glows RED when not in network.
Blinks RED during communication data transfer.
S
T
A
T
U
S
T
E
S
T
C
O
M
M
CONFIGURATOR
METERING MODULE
MODBUS MODULE
CONFIGURATOR
METERING MODULE
Содержание OMEGA
Страница 2: ...Stabilise systems with technology ...
Страница 4: ...Change course quickly ...
Страница 6: ...Match performance with prudence ...
Страница 8: ...Adopt technological brilliance ...
Страница 10: ...Keep an eye on upkeep ...
Страница 26: ...Matrix Protection Control Units T UW M X4 5 ...
Страница 70: ...Accessories ...
Страница 84: ...Control Circuit Wiring ...
Страница 92: ...Mounting Termination ...
Страница 135: ...SP 50567 R5 ...