82
8
System Operation
8.2
Check Sums - Hours of Operation
8.2.1
Calling the Checksums
Each of the parameter levels is safeguarded by its own checksum. The checksum for each
level and the safety and pre-purge times are displayed here in succession.
Order:
1
st
oil safety time in seconds
2
nd
oil safety time in seconds
1
st
gas safety time in seconds
2
nd
gas safety time in seconds
Pre-purge time in seconds
On the VMS without pilot burner the statement of the 2
nd
safety time contains safety time. The
statement of the 1
st
safety time is then irrelevant.
NOTICE
If the parameter has been changed, the checksum will change, too, if a total reboot has been
proceeded or the duration of 1h has passed.
Switch (1) to SETPOINT FEEDBACK
Press ENTER (3) and keep pressed
–
the display shows the checksum and the safety
times one after the other.
CRC 16 level
0: adjustable without password
1: adjustable by person commissioning
2: adjustable by the burner manufacturer or the boiler manufacturer
3: adjustable by LAMTEC only
4: adjustable by LAMTEC only
Содержание VMS Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...