99
8
System Operation
Fault
Code
No.
Restart according to
Description
TRD
EN676
451
1
1
Ignition position was left in ignition mode. Channel: 1
H/Ü
In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
452
1
1
Ignition position was left in ignition mode. Channel: 2
H/Ü
In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
453
1
1
Ignition position was left in ignition mode. Channel: 3
H/Ü
In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
454
1
1
Ignition position was left in ignition mode. Channel: 4
H/Ü
In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
455
1
1
Ignition position was left in ignition mode. Channel: 5
H/Ü
In case of a constant output:
Possible EMC influences due to ignition transformer; check the frequency converter
settings
500
0
0
Internal comparison: relay out terminal 67 not picking up.
H
Fault during an internal self-test.
Reset the fault; switch the mains voltage off and on again if necessary.
Check all fuses in the device.
If fault messages are constantly appearing one after the other <Symbol For-
mat="Symbol">
→
</Symbol> exchange the device or respective card.
501
0
0
Internal comparison: The relay output terminal 43 or 68 (ETAMATIC) does not
respond.
H
See S500
502
0
0
Internal comparison: relay out terminal 16 or 65 (ETAMATIC) not picking up.
H
See S500
503
0
0
Internal comparison: relay out terminal 11 or 66 (ETAMATIC) not picking up.
H
See S500
504
0
0
Internal comparison: relay out terminal 45 not picking up.
H
See S500
505
0
0
Internal comparison: relay out terminal 68 or 61 (ETAMATIC) not picking up.
H
See S500
506
0
0
Internal comparison: relay out terminal 36 (ETAMATIC K202) not picking up.
H
See S500
507
0
0
Internal comparison: relay out terminal 41 not picking up.
H
See S500
508
0
0
Internal comparison: relay out terminal 76 not picking up.
H
See S500
509
0
0
Internal comparison: Output K203 not picking up.
See S500
510
0
0
Internal comparison: Output K201 not picking up.
See S500
Содержание VMS Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...