38
6
Commissioning
6.5.5
Programming While The Burner Is Stationary
NOTICE
The monitoring values may clearly deviate from the values of the main processor, depending
on the configuration (redundant signals or not). It is essential that the actual value matches
the setpoint value of the respective processors, not the correspondance of values between
the processors.
NOTICE
Should there be any redundant feedbacks, the curves must be programmed on a burner
during operation.
Turn selector switch (1) to SETPOINT
Switch (4) up or down
until system is optimally adjusted at instantaneous firing
rate
on VMS 5
setpoint and actual value feedback are displayed
Switch (4) Channel 2 up or down until channel 5 is
optimally adjusted
Turn selector switch (1) to ACTUAL VALUE FEED-
BACK
the display shows the value of the external
feedback.
at the three-point-step channel the display shows
the same value as in the setpoint setting.
Press ENTER (3)
SZP-POINT appears on the display.
Содержание VMS Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...