67
6
Commissioning
6.8
Shut-off Limits
6.8.1
Run to Shut-off Limits
The VMS tolerance which was showed by every control system affects the positioning accu-
racy. These tolerances can be influenced by parameter settings.
When the combustion plant is adjusted, it has to be ensured that the flame burns safe and
stable under these tolerances. To verify that, it is necessary not only to check the pre-adjusted
setpoints of the fuel/air ratio settings but also to check the so-called shut-off limits. These are
the actuator values, which can be taken due to the permitted tolerances but not switch off.
This check is to be done for the whole firing rate range and operating range.
This may only be omitted when:
–
the plant is equipped with a failsafe CO or O
2
monitoring, which will automatically off the
burner when combustion is incomplete
or
–
the plant is equipped with a failsafe CO or O
2
monitoring, which will compensate the com-
bustion tolerances
or
–
it is ensured that the operating mode will have enough excess air through the whole range
and the tolerance of the burner control would be of no consequence.
or
–
the VMS parameters are set in such a way that the tolerances in air deficiency direction
has 0 digit, therefore only a tolerance for excess air exists.
WARNING!
If this shut-off limits check is omitted due to one of these reasons, the efficiency of the measure
is to be checked, e.g. check the stability of combustion in the preset shut-off limits in CO/O
2
monitoring.
WARNING!
Due to the evidences required by the authorities and bodies, quality management systems,
liability issues, etc, we highly recommend you to document the start-up of this shut-off limits.
Содержание VMS Series
Страница 1: ...www lamtec de Sensors and Systems for Combustion Technology Manual Fuel Air Ratio Control System VMS...
Страница 2: ......
Страница 119: ...118 10 Appendix...
Страница 121: ...120 10 Appendix 10 6 Process Sequence Charts Fig 10 3 Sequence of functions VMS digital inputs sequencer...
Страница 129: ...128 10 Appendix Fig 10 9 Ger t 4 Ger t 5 with output regulator...
Страница 141: ...140 10 Appendix 10 14 Declaration of Conformity...
Страница 142: ...141 10 Appendix...
Страница 143: ...142 10 Appendix 10 15 Protocol Example...
Страница 144: ...143 10 Appendix 10 16 O2 Setpoint Curves...
Страница 145: ...144 10 Appendix...