45
6
Commissioning
6.6.1.4 O
2
Limit Curve
You can set the monitoring bands’ parameters for 2 fuels, oil/gas, as a function of fuel. The
permitted deviation is calculated as a percentage of the setpoint. You can specify two separate
percentage values for base firing rate and full firing rate. The section between is interpolated
linearly.
Monitoring/shutdown times:
1
st
monitoring band: 120 seconds; active after “Control on”.
2
nd
monitoring band: 30 seconds; active after “Burner on”.
Factory setting
1
st
monitoring band, upward direction
–
Base firing rate (parameters 923 / 925) 60%
–
Full firing rate (parameters 924 / 926) 100%
1
st
monitoring band, downward direction
–
Base firing rate (parameters 927 / 929) 40%
–
Full firing rate (parameters 928 / 930) 50%
2
nd
monitoring band, downward direction (may be modified during commissioning)
–
Base firing rate (parameters 931 / 933) 50%
–
Full firing rate (parameters 932 / 934) 70%