FMS Commissioning
Programming Curves
Press Acceptance (3) again
Aids
-
burner ignites
-
sep. ignition point appears on display
Programming
Press Acceptance (3)
with burner stationary
-
ignition point 1 appears on display
nd
th
Programming 2 to 19 point
Selector switch (1) to "Load rating”
Run to desired load rating using channel 1 switch
Selector switch (1) to "set point”
Switch (4) up or down
until system is optimally adjusted at instantaneous load rating
E2,B1,C1
On FMS 5: Selector switch (1) to "Channel 5 display”
E12
-
set point and actual value feedback are displayed.
Switch (4) (channel 2) up or down
E12
-
until channel 5 is optimally adjusted
Selector switch (1) to "Actual value feedback”
Wait until feedback has stopped
Press Acceptance (3)
-
Point X appears on the display (X is the number of the
A16
th
programmed point. That is, at the 4 press of the
acceptance key, point 4)
________________________________________________________
A load point on the curve must be the lowest possible load
rating that can be pre-set by the load control unit in operation,
otherwise the compound cannot completely follow the load
control unit. The compound does not go below its lowest point
even in the event of lower load requirements.
________________________________________________________