104
FMS Fault Correction
Correction input ( F )
Aids
F1
___________________________________________________________________
Fault
121
The monitoring processor checks whether the present correction values
122
lies within the range set.
123
___________________________________________________________________
124
125
Check correction range
Otherwise A7
_____________________________________________________________________________________________________
F2
Fault
301
Correction input is configured for 4 … 20 mA, but the instantaneous
302
value is < 4 mA, wire possibly broken or connection poles transposed
Check wiring
Check parameter 431, 432
_____________________________________________________________________________________________________
F3
Selector switch on LR1 on "Measure”
Centre position potentiometer P4 on power unit LPE 1/S possibly set
incorrectly
at output 0…20 mA but no 10 mA
(see LR 1 operating instructions)
at output 4…20 mA but no 12 mA
Turn potentiometer to 10 or 12 mA (on LPE 1/S)
_____________________________________________________________________________________________________
F4
A value other than
The maximum correction range according to the standard software setting is
200 or +/-100 is displayed
200 points. Other range sizes are available for special cases, however.
_____________________________________________________________________________________________________
F5
50% is not displayed
Either 10 or 12 mA are not being fed to the FMS
Measure current
Check wiring
Otherwise as for F2 or F3
or
Jumpers are incorrectly inserted on the back of the front panel.
Check
_____________________________________________________________________________________________________
F6
Fault
381
The values of the correction input signals are compared between main and
382
monitoring processor.
Change processor card