Settings
List of Parameters
(Level 0 and 1 parameters only)
Para-
Short
Safety
Lower
Upper
meter-
design-
level
limit
limit
Standard
No.
nation
Description
values Aids
_____________________________________________________________________________________________________
711
BandV K4
1
0
50
Band shift
4
P3
Channel 4
712
BandV K5
1
0
50
Band shift
4
P3
Channel 5
Compound
718
Laufz L
1
0
65535
Running time in pts./min for TPS
9999
P12
Load input
In the event of load via current or
pot, the value must be 0
719
Laufz K1
1
0
65535
Running time in pts./min
9999
P13
for continuous output channel 1
720
Laufz K2
1
0
65535
Running time in pts./min
9999
P13
for continuous output channel 2
721
Laufz K3
1
0
65535
Running time in pts./min
9999
P13
for continuous output channel 3
722
Laufz K4
1
0 65535
Running time in pts./min
9999
P13
for continuous output channel 4
723
Laufz K5
1
0 65535
Running time in pts./min
9999
P13
for continuous output channel 5
729
stopVERB
1
10
100
Minimum compound running time
10
P15
in seconds
730
minTAKT1
1
1
100
Minimum cycle length for channel 1
1
P16
in 20ths seconds per digit (50 ms)
731
minTAKT2
1
1
100
Minimum cycle length for channel 2
1
P16
in 20ths seconds per digit (50 ms)
732
minTAKT3
1
1
100
Minimum cycle length for channel 3
1
P16
in 20ths seconds per digit (50 ms)
733
minTAKT4
1
1
100
Minimum cycle length for channel 4
1
P16
in 20ths seconds per digit (50 ms)
734
minTAKT5
1
1
100
Minimum cycle length for channel 5
1
P16
in 20ths seconds per digit (50 ms)
740
PauseT1
1
1
100
Minimum pause between channel 1 cycles 2
P27
in 20ths seconds per digit (50 ms)
741
PauseT2
1
1
100
Minimum pause between channel 2 cycles 2
P27
in 20ths seconds per digit (50 ms)
742
PauseT3
1
1
100
Minimum pause between channel 3 cycles 2
P27
in 20ths seconds per digit (50 ms)
743
PauseT4
1
1
100
Minimum pause between channel 4 cycles 2
P27
in 20ths seconds per digit (50 ms)
744
PauseT5
1
1
100
Minimum pause between channel 5 cycles 2
P27
in 20ths seconds per digit (50 ms)
24