FMS Commissioning
Programming Curves
Programming
Selector switch (1) to "Load rating”
Aids
last top point
Run to top load rating
-
999 on the display (corresponds to 20 mA on the load input)
D4, D6
________________________________________________________
It is essential to run to the highest load rating that can be pre-set
by the load control unit in operation, otherwise the compound
cannot completely follow the load control unit. The compound
does not go above its highest point even in the event of higher
load requirements
________________________________________________________
Selector switch (1) to "set point”
Switch (4) up or down
until system is optimally adjusted at instantaneous load rating
On FMS 5:
Selector switch (1) to "Channel 5 display”
-
set point and actual value feedback are displayed.
Switch (4) (channel 2) up or down
until channel 5 is optimally adjusted
Selector switch (1) to "Actual value feedback”
Wait until feedback has stopped
Press Acceptance (3)
-
Point X appears on the display
Store curve
Switch mode selector switch (2) from "Setting” to "Automatic”
-
"Memory” appears briefly on the display.
The curve has been transferred into the EEPROM
A5, A10
Check monitoring values
Mode selector switch (2) to "Monitoring display”
-
The display skips to the values of the monitoring section
Selector switch (1) to "Load rating”
Run to programmed load ratings
Selector switch to "Set-point” or "Actual value feedback”
For specimen report, see appendix page 149
________________________________________________________
The monitoring values may clearly deviate from the values of the
main processor, depending on the configuration (redundant signals
or not). What is important is that the actual value and set-point
value for the respective processor agree, not that there is
agreement between the values of different processors.
________________________________________________________
46
CHANNEL 1
CHANNEL 2 CHANNEL 3 CHANNEL 4
ENTER
POWER
OIL
GAS
ALARM
SETPOINT
FEEDBACK
SETPOINT
FEEDBACK
ACTUAL VALUE
FEEDBACK
ACTUAL VALUE
FEEDBACK
SETPOINT
CHANNEL 5
x
x
x
5
4
6
A
B
7
8
3
SETTING
AUTOMATIC
CLEAR
MEMORY
O -CONTROL
2
PARAMETERISATION
MONITORIN
DISPLAY
FEUERUNGS-MANAGEMENT-SYSTEM FMS
LAMTEC
LAMTEC
x
2
1
DISPLAY CHANNEL 5
(DIGITAL INPUTS)
LOAD RATING
(CORR. INPUT)
STATUS
(CORR. RANGE)
SETPOINT
i