TAURA D MCS
17
EN
cod. 3541A222 - Rev. 05 - 04/2013
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.
Service menu
The card Service Menu is accessed by pressing the Reset button for 20 seconds. 4 sub-
menus are available: press the Heating buttons to select, in increasing or decreasing or-
der, "tS", "In", "Hi" or "rE". "tS" means Transparent Parameters Menu, "In" means
Information Menu, "Hi" means History Menu: after selecting the submenu, press the Re-
set button again to access it; "rE" means History Menu Reset: see description.
"tS" - Transparent Parameters Menu
16 parameters indicated by the letter "P" are available: which are also modifiable from
Remote Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
3.
The Maximum Heating Power parameter can be modified also in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"In” - Information Menu
7 pieces of information are available.
Press the Heating buttons to scroll the list of information in increasing or decreasing or-
der. Press the DHW buttons to display the value.
Notes:
1.
In case of damaged sensor, the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu or exiting occurs automatically after 15 minutes.
"Hi" - History Menu
The card can store the last 11 faults: the History datum item H1: represents the most re-
cent fault that occurred; the History datum item H10: represents the least recent fault that
occurred.
The codes of the faults saved are also displayed in the corresponding menu of the Re-
mote Timer Control.
Press the Heating buttons to scroll the list of faults in increasing or decreasing order.
Press the DHW buttons to display the value.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 sec-
onds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"rE" - History Reset
Press the Eco/Comfort button for 3 seconds to delete all the faults stored in the History
Menu: the card will automatically exit the Service Menu, in order to confirm the operation.
Press the Reset button for 20 seconds to exit the card Service Menu, or exiting occurs
automatically after 15 minutes.
4.2 Startup
Before lighting the boiler
•
Check the seal of the gas system.
•
Check correct prefilling of the expansion tank.
•
Fill the water system and make sure all air contained in the boiler and the system
has been vented.
•
Make sure there are no water leaks in the system, DHW circuits, connections or boil-
er.
•
Check correct connection of the electrical system and efficiency of the earthing sys-
tem.
•
Make sure the gas pressure for heating is that required.
•
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Checks during operation
•
Switch the unit on.
•
Check the tightness of the fuel circuit and water systems.
•
Check the efficiency of the flue and air/fume ducts while the boiler is working.
•
Make sure the water is circulating properly between the boiler and the systems.
•
Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
•
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
•
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.
•
Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
•
Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
b05
Relay card LC32
operation selection (b02=1)
0=External gas valve
0=External gas
valve
0=External gas
valve
1=System filling solenoid
valve
2=Solar 3-way valve
No effect on adjustment (b02=2)
--
0
No effect on adjustment (b02=3)
--
0
No effect on adjustment (b02=4)
--
0
b06
Mains Voltage Frequency
0=50Hz
0=50Hz
0=50Hz
1=60Hz
b07
Comfort burner on time
(b02=1)
0-20 seconds
5 seconds
5 seconds
No effect on adjustment (b02=2)
--
5
No effect on adjustment (b02=3)
--
5
No effect on adjustment (b02=4)
--
5
b08
Driver Gas valve
0 = Standard, 1
0=Standard
0=Standard
Contents Description
Range
Default
TAURA D MCS
P01
Ignition ramp Offset
0-40
20
20
P02
Heating ramp
1-20°C/minute
5°C/minute
5°C/minute
P03
Heating standby time
0-10 minutes
2 minutes
2 minutes
P04
Heating Post-Circulation
0-20 minutes
6 minutes
6 minutes
P05
Heating user max. set point
31-85°C
80°C
80°C
P06
Max. power in heating
0-100%
100%
100%
P07
Burner shutdown in hot water production
(b02=1)
0=Fixed
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Burner shutdown in hot water production
(b02=2)
0=Fixed
0=Fixed
1=Linked to set point
2=Solar (5)
3=Solar (10)
4=Solar (20)
Hot water tank hysteresis (b02=3)
0-4°C
2°C
Hot water tank hysteresis (b02=4)
0-4°C
2°C
P08
DHW standby time (b02=1)
0-60 seconds
30 seconds
30 seconds
DHW standby time (b02=2)
0-60 seconds
60 seconds
DHW standby time (b02=3)
0-60 seconds
30 seconds
DHW standby time (b02=4)
0-60 seconds
30 seconds
P09
DHW user max. set point (b02=1)
50-65°C
50°C
50°C
DHW user max. set point (b02=2)
50-65°C
55°C
DHW user max. set point (b02=3)
50-65°C
65°C
DHW user max. set point (b02=4)
50-65°C
65°C
P10
Anti-inertia function temperature (b02=1)
70-85°C
70°C
70°C
No effect on adjustment (b02=2)
--
0
Delivery temperature in hot water production
(b02=3)
70-85°C
80°C
Delivery temperature in hot water production
(b02=4)
70-85°C
80°C
P11
Anti-inertia function Post-Circulation (b02=1) 0-5 Seconds
0 seconds
0 seconds
DHW Post-Circulation (b02=2)
0-60 Seconds
30 seconds
DHW Post-Circulation (b02=3)
0-60 Seconds
30 seconds
DHW Post-Circulation (b02=4)
0-60 Seconds
30 seconds
P12
Max. power in DHW
0-100%
100%
100%
P13
Absolute min. power
0-100%
0%
0%
P14
Post-Ventilation
0=Default
0=Default
0=Default
1=50 seconds
Contents Description
Range
Default
TAURA D MCS
P15
CO2 limit Offset (b03=0)
0 (Minimum)
30 (Maximum)
20
20
No effect on adjustment (b03=1)
--
20
No effect on adjustment (b03=2)
--
20
CO2 limit Offset (b03=3)
0 (Minimum)
30 (Maximum)
20
CO2 limit Offset (b03=4)
0 (Minimum)
30 (Maximum)
20
No effect on adjustment (b03=5)
--
20
P16
Exchanger protection activation
0=No F43
10°C/second
10°C/second
1-15=1-15°C/second
Con-
tents
Description
Range
t01
NTC Heating sensor (°C)
between 05 and 125 °C
t02
NTC Safety sensor (°C)
between 05 and 125 °C
t03
NTC DHW sensor (°C)
between 05 and 125 °C
t04
NTC External sensor (°C)
between -30 and 70°C (negative values flash)
L05
Actual burner power (%)
00%=Min., 100%=Max.
F06
Actual Flame resistance (Ohm)
00-99 Ohm (-- = burner off)
St07
Fan step (Number)
0=Off, 1=Min, 2=Med, 3=Max
Contents Description
Range
Default
TAURA D MCS