1.1 Special requirements for R32 refrigerant
:$51,1*
•
'R127KDYHUHIULJHUDQWOHDNDJHDQGRSHQIODPH
•
Be aware that the R32 refrigerant does NOT contain an odour.
:$51,1*
The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without conti-
nuously operating ignition sources (example:open flames,an operating gas appliance) and have a room size as
specified below.
NOTE
•
Do NOT re-use joints which have been used already.
•
Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes.
:$51,1*
0DNHVXUHLQVWDOODWLRQVHUYLFLQJPDLQWHQDQFHDQGUHSDLUFRPSO\ZLWKLQVWUDFWLRQVDQGZLWKDSSOLFDEOHOHJLVODWLRQ
(for example national gas regulation) and are executed only by authorised persons.
NOTE
Symbol m
c
denotes the refrigerant charge of a single refrigerating system. Where multiple refrigerating systems are servicing the same space, the refrige-
rating system with the largest refrigerant charge shall be used.
•
3LSHZRUNVKRXOGEHSURWHFWHGIURPSK\VLFDOGDPDJH
•
Installation of pipework shall be kept to a minimum.
If the total refrigerant charge in the system (m
c
) is
NJWKHUHDUHQRDGGLWLRQDOPLQLPXPIORRUDUHDUHTXLUH
-
ments.
,IWKHWRWDOUHIULJHUDQWFKDUJHLQWKHV\VWHPP
c
) is >1.842
NJ\RXQHHGWRFRPSO\ZLWKDGGLWLRQDOPLQLPXPIORRUDUHDUHTXLUHPHQWVDVGHVFULEHGLQWKHIROORZLQJIORZ
chart.
a
A
B
VA
min
VA
min
ш
1.8m
P
fig. 1 - indoor unit installation
The area of A plus B has to be greater than or equal to 4.5 m
2.
Legend
a
Indoor unit
A
Room where the indoor unit is installed.
B
Room adjacent to room A.
VA
min
n°2 openings (n°1 at the top and n°1 at the bottom) between Room A and Room B.
NOTE
6SDFHVFRQQHFWHGE\RQO\GURSFHLOLQJVGXFWZRUNRUVLPLODUFRQQHFWLRQVVKDOOQRWEHFRQVLGHUHGDVLQJOHVSDFH
For units mounted higher than 1,6 m, spaces divided by partition walls which are no higher than 1,6 m shall be considered a single space.
For fixed appliances, rooms on the same floor and connected by an open passageway between the spaces can be considered a single room when deter-
mining compliance to A
min
, if the passageway complies with all of the following .
•
It is a permanent opening.
•
It extends to the floor.