background image

FL D HF

10

EN

cod. 3541P701  -  Rev. 00  -  10/2018

4.4 Troubleshooting
Diagnostics

The boiler has an advanced self-diagnosis system. In case of a boiler fault, the display
will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdowns (marked with the letter "

A

"): to restore

operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed. At this point the display will show 

“d4” 

for about

30 seconds

 or 

“d5” 

for about 

5 minutes

 which indicates the waiting time after which the

boiler will resume normal operation. if the boiler fails to restart, it is necessary to eliminate
the fault.
Other faults cause temporary shutdowns (marked with the letter “

F

”) which are automat-

ically reset as soon as the value returns within the boiler's normal working range.

List of faults

Table. 8

5. TECHNICAL DATA AND CHARACTERISTICS

Table. 9- Legend, fig. 27, fig. 28 and fig. 29

Code

fault

Fault

Possible cause

Cure

A01

No burner ignition

No gas

Check the regular gas flow to the 
boiler and that the air has been elimi-
nated from the pipes

Ignition/detection electrode fault

Check the wiring of the electrode and 
that it is correctly positioned and free 
of any deposits

Faulty gas valve

Check the gas valve and replace it if 
necessary

Gas valve wiring disconnected

Check the wiring

Ignition power too low

Adjust the ignition power

A02

Flame present signal with 
burner off

Electrode fault

Check the ionisation electrode wiring

Card fault

Check the card

A03

Overtemperature protec-
tion activation

Heating sensor damaged

Check the correct positioning and 
operation of the heating sensor

No water circulation in the system Check the circulating pump

Air in the system

Vent the system

F04

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

F05

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

Fan fault

Wiring disconnected

Check the wiring

Defective fan

Check the fan

Card fault

Check the card

A06

No flame after the ignition 
phase

Low pressure in the gas system

Check the gas pressure

Burner minimum pressure setting Check the pressures

F07

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

A09

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F10

Delivery sensor 1 fault

Sensor damaged

Check the wiring or replace the sen-
sor

Wiring shorted

Wiring disconnected

F11

DHW sensor fault

Sensor damaged

Check the wiring or replace the sen-
sor

Wiring shorted

Wiring disconnected

F14

Delivery sensor 2 fault

Sensor damaged

Check the wiring or replace the sen-
sor

Wiring shorted

Wiring disconnected

A16

Gas valve fault

Wiring disconnected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

F20

Combustion control fault

Fan fault

Check the fan and fan wiring

Faulty baffle

Check the baffle and replace it if nec-
essary

Flue not correctly sized or 
obstructed

Check the flue

A21

Poor combustion fault

Fault F20 generated 6 times in the 
last 10 minutes

See fault F20

A23

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

A24

Card parameter fault

Wrong card parameter setting

Check the card parameter and modify 
it if necessary

F34

Supply voltage under 180V. Electric mains trouble

Check the electrical system

F35

Faulty mains frequency

Electric mains trouble

Check the electrical system

F37

Incorrect system water 
pressure

Pressure too low

Fill the system

Water pressure switch damaged 
or not connected

Check the sensor

F39

External probe fault

Probe damaged or wiring shorted

Check the wiring or replace the sen-
sor

Probe disconnected after activat-
ing the sliding temperature

Reconnect the external sensor or dis-
able the sliding temperature

A41

Sensor positioning

Delivery sensor or DHW sensor 
detached from the pipe

Check the correct positioning and 
operation of the sensors

F42

Heating sensor fault

Sensor damaged

Replace the sensor

F43

Exchanger protection trips.

No H

2

O system circulation

Check the circulating pump

Air in the system

Vent the system

F50

Gas valve fault

Modulating Operator wiring dis-
connected

Check the wiring

Faulty gas valve

Check the gas valve and replace it if 
necessary

A51

Poor combustion fault

Inlet/exhaust flue obstruction

Check the flue

5

Sealed chamber

44

Gas valve

10

System delivery - Ø 3/4”

56

Expansion vessel

11

System return - Ø 3/4”

74

System filling faucet

14

Safety valve

81

Ignition and detection electrode

16

Fan

95

Diverter valve

19

Combustion chamber

114

Water pressure switch

22

Burner

187

Fume baffle

27

Copper exchanger for heating and DHW

209

Hot water tank delivery

28

Fume manifold

210

Hot water tank return

29

Fume outlet collar

241

Automatic bypass

32

Heating circulating pump

278

Double sensor ( heating)

36

Automatic air vent

Code

fault

Fault

Possible cause

Cure

Содержание FL D HF24

Страница 1: ...cod 3541P871 Rev 00 10 2018 c od 3541P Rev 0 2018 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE RU EN 3...

Страница 2: ...domestic hot water production are only active with the optional hot water tank connect ed as indicated in sec 3 3 2 2 Control panel Panel fig 1 Control panel Key of panel fig 1 1 DHW temperature sett...

Страница 3: ...e and curve offset Press the reset button detail 6 fig 1 for 5 seconds to access the Sliding temperature menu the display shows CU flashing Use the DHW buttons detail 1 fig 1 to adjust the desired cur...

Страница 4: ...table and do not cause damage to the exchanger or other components and or materials of the boiler and system Do not use generic antifreeze fluids additives or inhibitors that are not specific for use...

Страница 5: ...peration requires fitting the baffles supplied with the unit Make sure boiler is properly fitted with the correct baffle if to be used A Baffle replacement with boiler not installed B Baffle replaceme...

Страница 6: ...856 1 B2X Intake from installation room and wall or roof exhaust IMPORTANT THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION FL D HF24 FL D HF32 Max permissible length 60 meq 48 meq Baffle to use...

Страница 7: ...ion current is forced to the pre calibration value of the absolute minimum current Offset parameter Parameter q01 6 Press the DHW buttons to adjust the parameter q01 until the minimum nominal pressure...

Страница 8: ...Open Chamber with fume thermo stat 2 Sealed Chamber with fume pres sure switch 3 Sealed Chamber Combustion con trol with fume thermostat on recuperator 4 LOW NOx Sealed Chamber Com bustion control wi...

Страница 9: ...or remote control Make sure the fuel consumption indicated on the meter matches that given in the technical data table in cap 5 Make sure that with no demand for heating the burner lights correctly o...

Страница 10: ...ve Check the gas valve and replace it if necessary F10 Delivery sensor 1 fault Sensor damaged Check the wiring or replace the sen sor Wiring shorted Wiring disconnected F11 DHW sensor fault Sensor dam...

Страница 11: ...26 RU cod 3541P701 Rev 00 10 2018 5 1 7 3 4 10 3 4 11 3 4 209 3 4 210 3 4 21 22 23 HF24 e HF32 24 HF32 25 HF24 HF32 700 400 0 1 2 3 4 330 195 200 200 195 200 200 36 131 66 65 102 155 10 209 7 210 11 7...

Страница 12: ...5 2 General view and main components fig 27 General view FL D HF24 fig 28 General view FL D HF32 700 709 400 117 110 120 81 100 65 66 66 65 36 102 32 44 14 22 278 16 27 19 36 95 81 5 114 56 187 74 29...

Страница 13: ...n gas pressure at burner G20 mbar 1 5 1 5 Max gas flow G20 m3 h 2 73 3 64 Min gas flow G20 m3 h 0 88 1 22 Burner nozzles G31 no x 11 x 0 79 15 x 0 79 Gas supply pressure G31 mbar 37 37 Max gas pressur...

Страница 14: ...ulating pump speed Pressure power diagrams FL D HF32 A LPG B NATURAL GAS Circulating pump head pressure losses FL D HF32 A Boiler pressure losses 1 2 and 3 Circulating pump speed A 8 9 10 11 12 13 14...

Страница 15: ...32 Heating circulating pump 44 Gas valve 72 Room thermostat optional 81 Ignition detection electrode 95 Diverter valve 114 Water pressure switch 138 External probe optional 139 Remote timer control o...

Страница 16: ...PMW D W Serial Number 1820KK0021 18 20 KK 0021 0DQXIDFWXUHU 0DQXIDFWXUHU DGGUHVV 0RGHO RGH 4QZ L 306 30 4Q L WPD 3Q 2 3Q 12 6HULDO QXPEHU DUFRGH 1 1 3URGXFWLRQ GDWH 6HH WKH PDQXDO 8 028693 868563 G 9...

Страница 17: ...RU 1 8 8 2 2 1 FL D HF A sez 3 3 2 2 1 1 1 2 3 4 5 6 7 8 9 10 11 12 Eco 13 14 15 16 17 11 1 d2 11 1 d1 Comfort 11 1 cap 4 4 11 1 d3 d4 d5 2 3 5 7 1 5 2 7 1 5 3 B sez 3 3 0 1 4 2 3 reset eco comfort 9...

Страница 18: ...t 7 1 ECO 12 1 7 1 3 1 6 1 5 CU 1 1 1 10 6 0 3 1 OF 1 1 7 6 1 5 6 7 A 1 1 2 8 1 0 F37 1 8 300 Fh 0 8 8 I I I I I I I I I I I I I I I I I I ECO 7 1 7 1 20 30 40 50 60 70 80 90 85 20 10 0 10 20 1 2 3 4...

Страница 19: ...8 1 9 9 3 3 1 3 2 B 2009 142 5 C 15 C A 3 3 B B 25 25 Fr 1 F 10 CaCO3 10 30 1KWMA11W 10 8 9 10 3 4 11 3 4 95 209 3 4 210 3 4 3 4 25 3 5 B B 3 3A B HAR H05 VV F 3x0 75 2 8 B 230 1 8 9 0 1 2 3 4 10 11 1...

Страница 20: ...5 6 72 139 155 10 kOhm 1 8 kOhm 138 3 4 5 6 A 1 2 B 3 2 1 4 5 6 C1X C3X 60 100 80 125 FL D HF24 5 FL D HF32 5 10 90 1 0 5 45 0 5 0 25 0 2 HF24 43 HF32 45 0 3 HF24 43 HF32 45 2 5 3 10 C1X C1X C3X C3X C...

Страница 21: ...2 1KWMA06K 2 0 2 0 4 0 45 1KWMA01K 1 2 2 2 45 1KWMA65A 1 2 2 2 90 1KWMA02K 2 0 3 0 90 1KWMA82A 1 5 2 5 90 1KWMA70U 1 5 2 5 1KWMA16U 0 2 0 2 1KWMA55U 3 0 T 1KWMA05K 7 0 1KWMA85A 2 0 1KWMA86A 5 0 80 80...

Страница 22: ...q01 10 8 q01 1 2 10 9 q01 10 15 Eco comfort 5 B TEST Eco Comfort 2 q02 q02 1 2 10 3 1 q01 q01 1 2 10 Eco Comfort 2 TEST TEST TEST 3 4 1 5 TEST 19 19 TEST 100 3 4 1 00 100 1 1 0 2 1 100 TEST TEST 3 TE...

Страница 23: ...1 190 2 450 3 700 b10 b02 1 0 1 10 0 b02 2 0 1 10 b02 3 b02 4 b11 b02 1 10 100 10 b02 2 10 100 10 15 b02 3 b02 4 b12 0 1 0 FL D HF P01 0 40 20 P02 1 20 C 5 P03 0 10 2 P04 0 20 6 P05 31 85 C 80 P06 0...

Страница 24: ...4 2 B cap 5 4 3 B 20 1 P15 CO2 b03 0 0 30 20 b03 1 b03 2 CO2 b03 3 0 30 CO2 b03 4 0 30 b03 5 P16 0 No F43 10 1 15 1 15 C P17 100 100 P18 0 100 100 60 P19 b02 1 0 20 C 10 b02 2 0 20 C b02 3 b02 4 P20...

Страница 25: ...A 6 1 1 d4 30 d5 5 F 8 5 9 27 28 29 A01 A02 A03 F04 F05 A06 F07 A09 F10 1 F11 F14 2 A16 F20 A21 F20 10 F20 A23 A24 F34 180 F35 F37 F39 A41 F42 F43 H2 O F50 A51 5 10 3 4 44 11 3 4 56 14 74 16 81 19 95...

Страница 26: ...very 3 4 11 System return 3 4 209 Hot water tank delivery 3 4 210 Hot water tank return 3 4 fig 21 Front view fig 22 Side view fig 23 Top view HF24 and HF32 fig 24 Top view HF32 fig 25 Bottom view HF2...

Страница 27: ...3541P701 Rev 00 10 2018 26 5 2 27 FL D HF24 28 FL D HF32 700 709 400 117 110 120 81 100 65 66 66 65 36 102 32 44 14 22 278 16 27 19 36 95 81 5 114 56 187 74 29 28 32 44 14 22 278 16 27 19 36 95 81 5 1...

Страница 28: ...9 9 P Pmax 80 60 C 93 0 93 1 30 90 5 91 0 NOx 3 150 NOx G20 x 11 x 1 35 15 x 1 35 G20 20 0 20 0 G20 12 0 12 0 G20 1 5 1 5 G20 3 2 73 3 64 G20 3 0 88 1 22 G31 x 11 x 0 79 15 x 0 79 G31 37 37 G31 35 0...

Страница 29: ...D HF24 A 1 2 3 FL D HF32 A B FL D HF32 A 1 2 3 A 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 35 30 25 20 15 10 5 kW mbar B 0 1 2 3 4 5 6 7 0 500 1 000 1 500 2 000 Q l h H m H 2 O A 3 2 1 A...

Страница 30: ...RU cod 3541P701 Rev 00 10 2018 5 6 30 A 16 32 44 72 81 95 114 138 139 155 278 81 1kW L N 230V 50 Hz 16 N L 32 L N T T 278 4 3 2 1 44 ABM01A 95 3 2 1 RED LIGHT BLUE WHITE 114 3 2 1 72 139 138 155 10kO...

Страница 31: ......

Страница 32: ...i VIA n 047 6 BRUCIATORI CALDAIE MURALI E TERRA A GAS GRUPPI TERMICI IN GHISA E IN ACCIAIO GENERATORI DI ARIA CALDA TRATTAMENTO ACQUA CONDIZIONAMENTO...

Отзывы: