Explanation of the operating elements  

Operation

 

10 

 

Frost protection function 

The frost protection circuit prevents the heating system 
from freezing by automatically switching on the pump. 
Flow sensor frost protection 
The frost protection function is activated if the flow 
temperature drops below 7°C. 
The frost protection function is deactivated if the flow 
temperature rises above 9°C. 
Outdoor sensor frost protection 
The frost protection function is activated if the outside 
temperature drops below 0°C. The pumps are activated 
and the burner is enabled. 

Temperature monitor operation 

The boiler pump runs continuously if boiler max. has been 
reached. Deactivation with 5k hysteresis. 

Pump-controlled return flow temperature increase 

ON: Return flow temperature < Minimum return flow 
temperature 
OFF: Return flow temperature > Minimum return flow 
tempe 5K or burner OFF. 

Mixer-controlled return flow temperature increase 

Mixer CLOSE = Heat is transported into heating system: 
Return flow temperature > Minimum return flow 
temperature.  
Mixer OPEN = Short circuit/blocking of generator: 
Return flow temperature < Minimum return flow 

temperature or [burner OFF and after-run time of pump 
has elapsed]. 

EEPROM check 

Every 10 minutes, a check is conducted automatically in 
order to establish whether the settings of the controller lie 
within the specified limits. If a value is found to be out-of-
range, it is substituted by the related default value. The 
range transgression is indicated by the flashing error 
number 81. 
In this case, the user should check the important settings 
of the controller. The error indication symbol goes out after 
the unit is restarted (RESET). 

Pump blocking protection 

The controller effectively prevents the pumps blocking 
following longer periods out of operation. The integrated 
protection function activates for 5 seconds all pumps that 
have not been in operation during the past 24 hours. 

Mixer motor blocking protection 

If the mixer was not moved for 24 hours, it is fully opened 
once only. The heating circuit pump is switched off during 
this time. The maximum flow temperature is monitored. 
Cancelled at maximum flow temperature – 5K. 

Delayed pump switch-off

 

 

When a heat generator is shut off the assigned pump runs 
on for 5 minutes. The return flow temperature increase 
pump is shut off immediately. 

Содержание Basic 0201 R V1

Страница 1: ...Lago Basic 0201 R V1 Heating module Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment...

Страница 2: ...null and void Important text passages Important information is highlighted with an exclamation mark E This attention symbol is used to point out dangers in this manual Installation Information on ins...

Страница 3: ...ar side 8 Functions 8 Operation in the cascade 8 Modulation in the cascade 8 Operation of a single heat generator 9 Stand alone 9 Single HS with Manager via CAN BUS 9 Modulation via air damper 9 Frost...

Страница 4: ...in cascade Air damper activation time s C D in the case of return flow temperature increase min return flow temperature H 1 2 11 Mod heat generator stages 1 single stage 2 two stage 11 2HS m modulati...

Страница 5: ...ls below the display with return flow temperature increase With return flow temperature increase sensor and mixer dynamic F K Mixer OPENS arrow points upward d Mixer CLOSES arrow points downward With...

Страница 6: ...the device Rotate the selection switch to RUN Automatic mode the mode is activated after 2 seconds List of the User Set Values Designation Area Factory IV Run Normal mode Display level with rotary kn...

Страница 7: ...re increase pump The setting 12 12K deviation 100 ID cannot be used for most mixer motors Small values cause the mixer to adjust quickly and can lead to oscillation Modulation H 1 2 11 Mod m Stand alo...

Страница 8: ...rs The controller can be used to actuate any of the following configurations A single stage heat generator with associated boiler pump and return flow temperature increase via pump or mixer 1 2 11 Mod...

Страница 9: ...temperature at Sensor T BOILER to the value T BOILER DES preset in the Manager Modulation via air damper The initial damper adjustment occurs with a delay of approx 3 minutes after a burner start Whil...

Страница 10: ...blocking of generator Return flow temperature Minimum return flow temperature or burner OFF and after run time of pump has elapsed EEPROM check Every 10 minutes a check is conducted automatically in...

Страница 11: ...General information Assembly Dismantling 11 Installation Installation Assembly Dismantling 3 x 0 5 a b c...

Страница 12: ...or an operating voltage of 230 V AC at 50 Hz The burner contact is a floating contact and must always be connected in series with the mechanical boiler thermostat 230V Relay switching capacity 2 2 A 2...

Страница 13: ...troller in cascade operation A Heat generator with temperature sensor KF and switch input T1 T2 B HS pump possibly in heating circuit flow C Return flow sensor VF D Mixer Temperature increase of retur...

Страница 14: ...ion location In the immersed pipe of the hot water cylinder tank generally on the front face of the tank Installation Slide the sensor as far as possible into the immersed pipe The immersed sleeve mus...

Страница 15: ...458 1607 100 C 339 1713 110 C 255 1823 120 C 194 1936 Errors When there is an error the corresponding error number flashes Resetting error number 81 Switch mains voltage Off and On again Error no Erro...

Страница 16: ...6 3 A Type of protection complying with DIN EN 60529 IP 40 Protection class complying with DIN EN 60730 Totally insulated Permitted ambient temperature during operation 0 to 50 C Permitted ambient te...

Отзывы: