background image

Explanation of the operating elements  

Operation

 

Settings via DIP switch (rear side) 

!

  Settings 1-5 => In V1 without function 

Sensor selection (5K NTC <-

> 1K PTC

Check the installed sensors (imprint, type plate, or 
measurement value - see table) and set the switch 
accordingly. 

Functions 

Functions 

!

  In V1, only stand-alone operation and operation with a 

cascade controller/manager is supported 
(also applies to individual heat generators). 

 

Operation in the cascade 

Function only with cascade manager via CAN BUS 

Settings: 
1/2/11/Mod = Depending on heat generator 
BUS-ID = 01-88 (cascade) 

Settings on the cascade controller: 
HS1 Type = Cascade modulating or switching 
HS1 BUS = CAN BUS 

The controller can be used as a heating module for the 
operation of switching and modulating (air damper) oil or 
gas heat generators in cascades with 1 to 8 heat 
generators (or 09-64 heat generators; only with 
corresponding cascade managers). The controller can be 

used to actuate any of the following configurations: 

  A single stage heat generator with associated 

boiler pump and return flow temperature increase 
via pump or mixer (1/2/11/Mod =1) 

  A two-stage heat generator with associated boiler 

pump and return flow temperature increase via 
pump or mixer (1/2/11/Mod =2) 

  A two-stage heat generator with associated boiler 

pump and shared return flow temperature increase 
via pump or mixer (1/2/11/Mod =11) 

  A modulating heat generator with associated boiler 

pump (1/2/11/Mod =m) 

Modulation in the cascade

 

 

In the case of a cascade, an air damper position is 
assigned to the required degree of modulation. The air flap 
is driven for the defined activation time => The mixer 
OPEN/CLOSE relays (here air damper connection) are 
actuated for the calculated period. => Only one qualitative 
control process is performed (more/less output). The heat 
generator will not deliver the exact degree of modulation 
required. 

!

  The air damper activation time must be set under 

switch position "

v

 

b

".

 

Air damper position: 
0-10% = CLOSE; 100% = OPEN; Intermediate values in 
increments 

Содержание Basic 0201 R V1

Страница 1: ...Lago Basic 0201 R V1 Heating module Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment...

Страница 2: ...null and void Important text passages Important information is highlighted with an exclamation mark E This attention symbol is used to point out dangers in this manual Installation Information on ins...

Страница 3: ...ar side 8 Functions 8 Operation in the cascade 8 Modulation in the cascade 8 Operation of a single heat generator 9 Stand alone 9 Single HS with Manager via CAN BUS 9 Modulation via air damper 9 Frost...

Страница 4: ...in cascade Air damper activation time s C D in the case of return flow temperature increase min return flow temperature H 1 2 11 Mod heat generator stages 1 single stage 2 two stage 11 2HS m modulati...

Страница 5: ...ls below the display with return flow temperature increase With return flow temperature increase sensor and mixer dynamic F K Mixer OPENS arrow points upward d Mixer CLOSES arrow points downward With...

Страница 6: ...the device Rotate the selection switch to RUN Automatic mode the mode is activated after 2 seconds List of the User Set Values Designation Area Factory IV Run Normal mode Display level with rotary kn...

Страница 7: ...re increase pump The setting 12 12K deviation 100 ID cannot be used for most mixer motors Small values cause the mixer to adjust quickly and can lead to oscillation Modulation H 1 2 11 Mod m Stand alo...

Страница 8: ...rs The controller can be used to actuate any of the following configurations A single stage heat generator with associated boiler pump and return flow temperature increase via pump or mixer 1 2 11 Mod...

Страница 9: ...temperature at Sensor T BOILER to the value T BOILER DES preset in the Manager Modulation via air damper The initial damper adjustment occurs with a delay of approx 3 minutes after a burner start Whil...

Страница 10: ...blocking of generator Return flow temperature Minimum return flow temperature or burner OFF and after run time of pump has elapsed EEPROM check Every 10 minutes a check is conducted automatically in...

Страница 11: ...General information Assembly Dismantling 11 Installation Installation Assembly Dismantling 3 x 0 5 a b c...

Страница 12: ...or an operating voltage of 230 V AC at 50 Hz The burner contact is a floating contact and must always be connected in series with the mechanical boiler thermostat 230V Relay switching capacity 2 2 A 2...

Страница 13: ...troller in cascade operation A Heat generator with temperature sensor KF and switch input T1 T2 B HS pump possibly in heating circuit flow C Return flow sensor VF D Mixer Temperature increase of retur...

Страница 14: ...ion location In the immersed pipe of the hot water cylinder tank generally on the front face of the tank Installation Slide the sensor as far as possible into the immersed pipe The immersed sleeve mus...

Страница 15: ...458 1607 100 C 339 1713 110 C 255 1823 120 C 194 1936 Errors When there is an error the corresponding error number flashes Resetting error number 81 Switch mains voltage Off and On again Error no Erro...

Страница 16: ...6 3 A Type of protection complying with DIN EN 60529 IP 40 Protection class complying with DIN EN 60730 Totally insulated Permitted ambient temperature during operation 0 to 50 C Permitted ambient te...

Отзывы: