background image

General information

 

Assembly / Dismantling

 

 

Operation of a single heat generator 

Settings: 
1/2/11/Mod = m (Modulation) 
1/2/11/Mod = 1 (switching heat generator) 
BUS-ID = -1 (single HS with desired temperature 
presetting) 

Settings on the Manager/Cascade controller: 
HS1 Type = Single stage HS switching! 
HS1 BUS = CAN BUS 

Stand alone 

The heat generator is activated once the temperature 
drops below the set temperature.  
Deactivation occurs at T-Des + 5K. 

Modulation: The mixer relays regulate the desired 
temperature of the heat generator by adjusting the air 
damper. 

Single HS with Manager via CAN BUS  

The burner is switched according to Manager presettings  

Modulation: The mixer relays regulate the temperature at 
Sensor T-BOILER to the value 
T-BOILER DES preset in the Manager. 

Modulation via air damper 

The initial damper adjustment occurs with a delay of 
approx. 3 minutes after a burner start. While "Burner OFF" 

and during the first three minutes after "Burner ON", the air 
damper is constantly driven towards in "CLOSE" direction. 

Connection 

During this operating condition, the relays T3 T4 is 
switched in parallel with the HS pump => When the HS 
provides the potential (L1´) for the air damper relays, it is 
connected to the terminal L1´ on the controller. The HS 
pump is then connected to T3 (= pump phase and bridge 
T4 to power supply phase L1). The air damper for 
modulation is connected to the contacts 5 (OPEN), 6 
(CLOSE) and 8 (potential). 

 
Enables burners 1+2 
5+6+8 air damper (N = 10) 
-> 5= Damper OPEN 
(warmer) 
-> 6= Damper CLOSE 
(colder) 
-> 8= Supply for damper 
11 HS pump (N = 10) 
9+12 Bridge 
(supply for HS pump) 

Содержание Basic 0201 R V1

Страница 1: ...Lago Basic 0201 R V1 Heating module Operating and Installation Instructions Please observe the safety instructions and read through this manual carefully before commissioning the equipment...

Страница 2: ...null and void Important text passages Important information is highlighted with an exclamation mark E This attention symbol is used to point out dangers in this manual Installation Information on ins...

Страница 3: ...ar side 8 Functions 8 Operation in the cascade 8 Modulation in the cascade 8 Operation of a single heat generator 9 Stand alone 9 Single HS with Manager via CAN BUS 9 Modulation via air damper 9 Frost...

Страница 4: ...in cascade Air damper activation time s C D in the case of return flow temperature increase min return flow temperature H 1 2 11 Mod heat generator stages 1 single stage 2 two stage 11 2HS m modulati...

Страница 5: ...ls below the display with return flow temperature increase With return flow temperature increase sensor and mixer dynamic F K Mixer OPENS arrow points upward d Mixer CLOSES arrow points downward With...

Страница 6: ...the device Rotate the selection switch to RUN Automatic mode the mode is activated after 2 seconds List of the User Set Values Designation Area Factory IV Run Normal mode Display level with rotary kn...

Страница 7: ...re increase pump The setting 12 12K deviation 100 ID cannot be used for most mixer motors Small values cause the mixer to adjust quickly and can lead to oscillation Modulation H 1 2 11 Mod m Stand alo...

Страница 8: ...rs The controller can be used to actuate any of the following configurations A single stage heat generator with associated boiler pump and return flow temperature increase via pump or mixer 1 2 11 Mod...

Страница 9: ...temperature at Sensor T BOILER to the value T BOILER DES preset in the Manager Modulation via air damper The initial damper adjustment occurs with a delay of approx 3 minutes after a burner start Whil...

Страница 10: ...blocking of generator Return flow temperature Minimum return flow temperature or burner OFF and after run time of pump has elapsed EEPROM check Every 10 minutes a check is conducted automatically in...

Страница 11: ...General information Assembly Dismantling 11 Installation Installation Assembly Dismantling 3 x 0 5 a b c...

Страница 12: ...or an operating voltage of 230 V AC at 50 Hz The burner contact is a floating contact and must always be connected in series with the mechanical boiler thermostat 230V Relay switching capacity 2 2 A 2...

Страница 13: ...troller in cascade operation A Heat generator with temperature sensor KF and switch input T1 T2 B HS pump possibly in heating circuit flow C Return flow sensor VF D Mixer Temperature increase of retur...

Страница 14: ...ion location In the immersed pipe of the hot water cylinder tank generally on the front face of the tank Installation Slide the sensor as far as possible into the immersed pipe The immersed sleeve mus...

Страница 15: ...458 1607 100 C 339 1713 110 C 255 1823 120 C 194 1936 Errors When there is an error the corresponding error number flashes Resetting error number 81 Switch mains voltage Off and On again Error no Erro...

Страница 16: ...6 3 A Type of protection complying with DIN EN 60529 IP 40 Protection class complying with DIN EN 60730 Totally insulated Permitted ambient temperature during operation 0 to 50 C Permitted ambient te...

Отзывы: