background image

 

 

Description: 

Alfa(net) 51 PI -50/+50°C 

Pages: 

Doc.no: 

180142 

Type: 

Manual 

By: 

BVDB 

Doc.Version: 

1.1 

File: 

Do180142 ALFANET 51 PI 6M -

50_+50grC Flash V11 EN.docx 

Signed: 

 

Date: 

26-10-2021 

VDH Products BV

 

Software 

151123

 

SW.Version 

V3.01 

 

Manual                   

ALFA(NET) 71 PI 

-50/+50°C

 

1

 

Function 

The ALFA(NET) 51 PI is a DIN-rail mounting thermostat-
unit,  with  an  analog  0-10Vdc  PI-output,  selectable  for 
function: Cool and/or Heat. 

The thermostat has also three relays outputs selectable for function cooling, heating or alarm. The 
temperature  is  being  measured  by  an  SM811  2-Wire  temperature  sensor.  The  range  of  the 
thermostat is -50/+50°C 
The ALFANET 51 PI is provided with an RS-485 network connection and can be readout or set by an 
PC with the ALFANET program connected thru an ALFANET PC-Interface. 

2

 

Installation 

On the connection diagram of the ALFA(NET) 51 PI is shown how the sensors, analogue output, power 
supply, relays and optional network are to be connected. After connecting the ALFA(NET) 51 PI to the 
power supply, a  self-test function is started. As this test is finished, the measured temperature 
appears in the display. 

3

 

Control 

The ALFA(NET) 51 PI thermostat can be controlled by four pushbutton on the front. These keys are;  

SET 

 

- view / change set value and reset alarm. 

∏ UP     

- increase set value. 

π DOWN  

- decrease set value. 

MODE 

- relay status key. 

4

 

Viewing setpoint 

By pushing the SET key the setpoint appears in the display. The decimal point of the last display starts 

blinking. A few seconds after releasing the SET key the setpoint disappears and the measured temperature is 

shown again in the display.

 

 

Содержание ALFA 51 PI

Страница 1: ...out or set by an PC with the ALFANET program connected thru an ALFANET PC Interface 2 Installation On the connection diagram of the ALFA NET 51 PI is shown how the sensors analogue output power supply relays and optional network are to be connected After connecting the ALFA NET 51 PI to the power supply a self test function is started As this test is finished the measured temperature appears in th...

Страница 2: ...DOWN keys after releasing the SET key Pressing the SET key again displays the maximum control value P43 in percentages which can now be adjusted with the UP and DOWN keys after releasing the SET key By pressing the SET key again the measured temperature is shown in the display again About 15 seconds after releasing the keys the measured temperature is shown in the display 7 Status of the relays By...

Страница 3: ...chnical data Type ALFA 51 PI 50 50 C or ALFANET 51 PI 50 50 C Range 50 50 C readout per 0 1 C Supply 100 240 Vac 50 60Hz max 10VA Display 3 digit 7 segment LED display Sensor SM 811 2 Wire PTC 1000Ω 25 C Relays Ry1 SPST NO 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Ry2 SPST NO 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Ry3 SPDT NO NC 250V 8A cosphi 1 or 250V 5A cosphi 0 4 Relays have one common C Analogue...

Страница 4: ...m P01 1 3 2 03 Function Relay 3 same as parm P01 1 3 3 04 Function PI output 1 Cool 2 Heat 3 Cool and Heat 1 3 1 05 Offset temperature sensor Calibration 15 15 0 C 0 0 06 Offset PI 15 15 0 C 0 0 07 P band setting 0 0 20 0 C 5 0 08 I time setting I action not active at P08 0 of P04 3 0 99 Minutes 0 off 10 Switch on stage two 0 Temp 1 Time 0 11 Switch on stage three 0 Temp 1 Time 0 12 Switch on dela...

Страница 5: ...larm 0 1 0 36 Reset alarm relay after recovering alarm 0 No 1 Yes 0 37 Reset alarm relay after manual reset 0 No 1 Yes 0 40 Start up delay after power failure 0 99 Minutes 0 41 Forced relay function at sensor failure 0 None 1 Cool 2 Heat 0 2 0 42 43 45 Minimum control value Maximum control value Apply minimum and maximum control value 0 100 0 100 0 No 1 Yes 0 100 0 90 Network number only at ALFANE...

Страница 6: ...ALFA NET 51 PI 50 50 C Doc no 180142 version 1 1 Pagina 6 van 8 13 Function diagram ...

Страница 7: ...ALFA NET 51 PI 50 50 C Doc no 180142 version 1 1 Pagina 7 van 8 14 Connections ...

Страница 8: ...Doc no 180142 version 1 1 Pagina 8 van 8 15 Dimensions 16 Address VDH Products B V Tel 31 0 50 30 28 900 Productieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: