background image

Page 36

LAARS Heating Systems

Gas valve regulation problems can also cause

delayed ignitions. See “Gas valve calibration”.

Incorrect gas orifice – Check orifice size.

A defective burner can cause a delayed ignition

during operation or at shutdown. If the gas supply

pressure is proper the gas valve is functioning

properly and the gas orifice is correct, the burner

should be inspected. To inspect it, remove the blower.

The burner is retained by the blower and it will drop

out of the bottom of the chamber when the blower is

removed. There should be no distortion or perforations

in the burner other than the punched holes. Replace if

indicated.

11.2 Short Cycling

Possible causes

a.

Reduced system flow - EDP

b.

Thermostatic union (EDP) or anti-condensing

valve not opening (EBP).

c.

T-T wires cross connected (jumped) – 

improper

installation -

 EBP or EDP/EDN

d.

Leakage of flue products into the combustion air

stream – Direct Vent Installations only, see

Section 9.2.3, Resolving Lockouts.

11.3 Noisy Operation

There are two principal sources of noisy

operation:

a.

Combustion - high pitched noise - whistle or

hoot.

b.

Boiling (kettling) - lower frequency noise which

varies with temperature - moan.

Many times it is difficult to determine the source

of the noise or if it is combustion related or boiling

related. Combustion noises always have the same

frequency; however, their volume may change from

the time that the burner first fires to the time that it

shuts off. A boiling noise is identified by rapidly

raising or lowering the system water pressure while

the noise is present. A change in the pitch or intensity

of the noise indicates a boiling problem.

Combustion noise

 occurs at any boiler

discharge temperature and is heard the loudest at the

flue outlet (especially on units that are sidewall

vented). There are two basic causes for the noise, rich

mixture (high CO

2

 or low O

2

) or cross contamination.

The mixture is determined by measuring the percent

O

2

 or CO

2

 in the flue products. O

2

 readings lower than

4½ % or CO

2

 readings higher than 9¼ % (natural gas)

and 10.8% (LP) will often cause combustion related

noise. The rich mixture could be caused by the mis-

calibration of the gas valve (offset adjustment) or by

the gas orifice size. To eliminate the noise; first, check

the gas valve calibration. If it is correct, install a

smaller gas orifice so that the O

2

 will rise above 4½%

or the CO

2

 will drop to 8½% (natural) or 9½% (LP).

The CO

2

 & O

2

 readings may be influenced by

cross contamination. Suspect cross contamination if

the noise returns when the front panel is replaced.

Boiling (kettling)

 may occur at boiler discharge

temperatures from 170°F to 210°F. The temperature at

which it starts will vary from one installation to

another. The primary cause of the problem is poor heat

transfer on the inside of the boiler coil. This may be

caused by foaming due to excessive concentration of

antifreeze in the system or by scaling from the boiler

water due to hardness of make up water.

Plumbing antifreezes should never be used in a

boiler system. Only boiler antifreezes, with effective

antifoamants, are appropriate for the ENDURANCE

boilers.

NOTE:

 The concentration of appropriate antifreeze

should be always be kept as low as possible to
minimize its effect on heat transfer and efficiency.

The method for eliminating the boiling noise is

the same regardless of the cause. However, if

antifreeze in the system is suspected of being the

cause, the concentration (<35%) and type should be

investigated.

Moisture

Although it is not a primary cause of lockouts,

moisture in the combustion chamber may cause

lockouts by weakening the flame signal to the boiler

control. It should be suspected if the boiler

temperature does not rise above 160°F during long

periods of operation. This condition can be caused by

a defective thermostat in the thermostatic union of

EDN or EDP boilers (or the omission of the

thermostatic union at installation) or failure of the

anticondensing valve in the EBP (combi) boilers.

Moisture can also get into the combustion chamber

through an incorrectly pitched or incorrectly installed

flue pipe (pitched back toward the boiler without a

condensate trap). The flue assembly of EBP, EDN and

EDP boilers installed as Direct Vent boilers should

always pitch down from the boiler.

11.4 Insufficient Hot Water (EBP only)

Possible cause:

a.

No flow restrictor (supplied with unit - field

installed)

b.

Water flow switch failure

c.

Mixing valve setting or failure

d.

Domestic hot water (DHW) heat exchanger

contamination

The most common cause for insufficient hot

water complaints results from failure to install a flow

restrictor. The absence of a flow restrictor allows

water to pass through the heat exchanger at a greater

rate than the boiler output is capable of heating to the

desired temperature.

Содержание EBP0110

Страница 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Страница 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Страница 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Страница 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Страница 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Страница 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Страница 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Страница 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Страница 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Страница 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Страница 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Страница 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Страница 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Страница 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Страница 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Страница 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Страница 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Страница 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Страница 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Страница 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Страница 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Страница 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Страница 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Страница 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Страница 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Страница 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Страница 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Страница 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Страница 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Страница 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Страница 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Страница 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Страница 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Страница 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Страница 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Страница 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Страница 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...

Страница 38: ...Repair Kit 2400 538 2400 538 16 Anti Condensing Valve Operator Only 2400 539 2400 539 17 Water Flow Switch 2400 542 2400 542 18 Safety Limit 230 F 2400 550 2400 550 2400 550 2400 550 2400 550 2400 55...

Страница 39: ...Endurance Page 39...

Страница 40: ...x 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 ww...

Отзывы: