6.4. These do not show on the control display, but it is

helpful to know how they affect the control logic of

the Endurance units.

6.5.1 ACV Release (EBP only)

When the EBP is in tank charge mode, and there

is a call for space heating, the EBP needs to know at

what temperature it can release the ACV (anti-

condensing valve) back to the space heating position,

allowing the hot water to go into the system. The ACV

release point is the “burner off” point minus 5°F

(3°C). For example, if the “burner off” point is 190°F

(88°C), the ACV release point is 185°F (85°C). This

means that when the supply temperature reads 185°F

(85°C) in the tank, it will release the ACV for heating

mode.

6.5.2 Tank Charge Setting (EBP only)

When the temperature at the tank sensor goes

below the tank charge setting, the EBP will be in “tank

charge” mode. The tank charge setting equals the

programmed “burner off” point minus a fixed 40°F

(22°C) differential. For example, if the “burner off”

point is 190°F (88°C), the EBP will go into “tank

charge” mode when the tank sensor reads below 150°F

(66°C). The ACV will close, and the EBP will run to

bring the supply temperature up to 185°F (85°C), and

the ACV will be released back to the space heating

mode (as long as there is no call for domestic hot

water).

6.5.3 Burner On Point

The “Burner On” point is calculated by

subtracting the “Burner On Differential (Dif)” from

the “Burner Control Point.” For EBP units the

differential is fixed at 13°F (7°C) and for EDP/EDN

units, it is adjustable (shown as “Dif” in the setup

menu) from 4°-30°F (2°-17°C). This value tells the

Endurance when to re-energize during a call for heat

in which the Endurance reached its “Burner Off

Point.”

6.5.4 Modulation Point

During a call for heat, the Endurance will ignite

at low fire and will begin to modulate to match the

load as it approaches the “Burner Control Point.”

There is no fixed temperature when this will occur,

and this value is not displayed on the Endurance.

6.6 Other Control Functions

6.6.1 Using Buttons on Control

Figure 30 shows a drawing of the control,

including the placement of the four buttons. Table 4

shows the actions associated with each of the buttons.

6.4.5 “Oal” Minimum Outdoor

Reset Point

The “Oal” parameter tells the controller what the

minimum allowable supply temperature can be,

regardless of the outdoor reset calculation.

For EDP/EDN units, the default setting is 170°F

(77°C) and it is adjustable 155-200°F (68-93°C).

For EBP units, the default setting is 170°F

(77°C) and it is adjustable 170-200°F (77-93°C). Note

that the difference between EBP and EDP/EDN

adjustment ranges is because the EBP units must be

able to keep the transfer tank at a high enough

temperature to generate the domestic water through

the DHW heat exchanger.

6.4.6 “rc” Outdoor Reset Ratio

The outdoor reset ratio is shown as “rc” in the

display. The ratio determines part of the relationship

between the outdoor temperature and the Endurance

supply temperature. It is adjustable between 0.1 and 5.

The reset number represents the increase in the

Calculated Setpoint (CSP)for every degree below the

warm outdoor shutdown temperature.

The boiler control calculates CSP = Oal + (oTo –

air temp) x rc.

6.4.7 “oTo” Warm Outdoor Shutdown

When in the outdoor reset function is on, the

control has the ability to shut down the boiler system

when the outdoor temperature sensor reads the “oTo”

temperature that is set. This parameter is adjustable

from 55°-70°F (13°-21°C) and has a default setting of

65°F (18°C). The warm outdoor shutdown feature

will, of course, not affect the generation of domestic

water in the EBP models.

6.4.8 “un

I

” Temperature Units

The control has the ability to display and be

programmed in both °F (Fahrenheit) or °C (Celsius).

The “unl” lets the user choose between °F and °C.

6.4.9 “Dif” Burner On Differential

The differential between the Burner Control

Point and the Burner On Point is shown as “Dif” in the

display. If the Endurance reaches the Burner Off Point

during a call for heat, and the call for heat continues,

this differential will determine at what point below the

Burner Control Point the Endurance will energize

again. In the EBP models, this differential is fixed at

13°F (7°C) to ensure that the transfer tank will be

properly charged. In the EDP/EDN models, this

differential is adjustable 4°-30°F (2°-17°C).

6.5 Calculated Control Values

There are several control values that are not

directly set by the user, but are calculated by the boiler

control, once the user has set the parameters in Section

Содержание EBP0110

Страница 1: ...llation and maintenance Improper installation and or operation could create carbon monoxide gas in flue gases which could cause serious injury property damage or death Improper installation and or ope...

Страница 2: ...elay 24 6 4 4 Oar Outdoor Reset 24 6 4 5 Oal Minimum Outdoor Reset Point 25 6 4 6 rc Outdoor Reset Ratio 25 6 4 7 oTo Warm Outdoor Shutdown 25 6 4 8 unl Temperature Units 25 6 4 9 Add Control Address...

Страница 3: ...with the gas to the burner flame holder Both the intake air and the gas are metered through separate orifices before entering the combustion air blower The blower forces the air fuel mixture through t...

Страница 4: ...rain etc during appliance operation or service circulator replacement control replacement etc 1 5 Clearances The dimension and criteria in Table 1 should be followed when choosing the location for the...

Страница 5: ...ate the opening centerline 16 1 2 42cm above grade use optional concentric vent terminal extension part number 2400 428 shown in Figure 7 In the U S vent terminals must be at least 3 feet 0 9m above a...

Страница 6: ...rements are from the centerlineof the venting to the boiler top or face of outside wall Dimensions shown in inches Configuration 2 Maximum horizontal 38 Maximum vertical 16 Measurements are from the c...

Страница 7: ...Endurance Page 7 Figure 7 Concentric Vent Parts Dimensions shown in inches...

Страница 8: ...tlet See note 4 3 feet 91 cm J Clearance to nonmechanical air supply Direct Vent Only 12 inches 30 cm inlet to building or the combustion air inlet Other Than Direct Vent 4 feet 1 2 m below or 36 inch...

Страница 9: ...atFab Inc under the trade name of Saf T Vent by Z Flex under the trade name of Z Vent and by ProTech Systems Inc under the trade name FasNSeal Follow the special gas vent manufacturer s instructions r...

Страница 10: ...Page 10 LAARS Heating Systems Figure 13 3 Vent Parts Dimensions shown in inches...

Страница 11: ...r boilers that are getting all of their combustion air from inside the building The confined space shall be provided with two permanent openings communicating directly with other spaces of sufficient...

Страница 12: ...reen can be used One portion of this assembly connects to the 5 air collar with a screen for the combustion air and the other part connects to the 3 flue opening see Figure 14 The rest of the 3 vent s...

Страница 13: ...ocal requirements 3 Install drip leg ground joint union and drip cap to trap sediment and for test gauge access 4 Support all piping with proper hangers 5 All threaded joints should be coated with pip...

Страница 14: ...e domestic potable water temperature has fallen below 39 4 C If this condition is recognized the Endurance pump will run for 5 minutes or until the boiler water temperature reaches 45 F 7 C If the boi...

Страница 15: ...Endurance Page 15 Figure 19 Hydronic Piping EDP EBP with Zone Valves Figure 20 Piping Single EDP EBP Boiler for Multiple Temperature Systems Figure 21 Piping Model EDP EDN for Radiant Floor...

Страница 16: ...Install an air purger in flow supply line as shown in piping diagrams 5 Install automatic float type air vent on air scoops Figure 22 Hydronic Piping EBP EDP for Systems Zoned with Circulators Figure...

Страница 17: ...ipped with a Low Temperature control feature that recognizes when the water temperature at the outlet of the boiler has fallen below 39 F 4 C If this condition is recognized the Endurance pump will ru...

Страница 18: ...y hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS D...

Страница 19: ...s il n y a pas d odeur de gaz pr s du plancher car le gaz est plus lourd que l air et peut se d poser sur le plancher QUE FAIRE EN CAS D ODEUR DE GAZ N essayez pas d allumer n importe quelque apparei...

Страница 20: ...tch Neutral leg to white wire Ground wire can be connected to the grounding screw in the box or on the switch 2 For single zone installations If external pump is required e g because of large system p...

Страница 21: ...Clock Thermostats That Require 24 VAC RELAY 24 VOLT NO CONTACT LAARS P N 2400 060 TO T T BOILER CONNECTIONS 120V 24 20VA W Y G R Rc L1 HOT L2 120 VAC TRANSFORMER NOTE This wiring required only for sin...

Страница 22: ...rner On Point that is calculated by subtracting the Burner On Differential from the Burner Control Point The Burner On Differential is adjustable from 4 to 30 F 2 to 17 C in the EDP EDN models and is...

Страница 23: ...ic Example Figure 32 EDP EDN Flow Schematic 6 Calculated Setpoint for Outdoor Reset shown as CSP when used The temperature that the controller has calculated for a setpoint based on the outdoor temper...

Страница 24: ...This parameter shown as PO in the selection screen allows the user to choose between the Endurance pump running continuously Con or running in the automatic mode Aut such that the pump is energized on...

Страница 25: ...ach of the buttons 6 4 5 Oal Minimum Outdoor Reset Point The Oal parameter tells the controller what the minimum allowable supply temperature can be regardless of the outdoor reset calculation For EDP...

Страница 26: ...g system T T call for heat Domestic hot water DHW call for heat Error condition detected Supply temperature detected as less than boiler on point 6 6 7 Anti Condense Valve Operation The control on the...

Страница 27: ...etween the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes dryers and any appliance not connected to the com...

Страница 28: ...en all supply and return valves 2 Fill heating system to minimum operating pressure 12 psig 3 Loosen screw in coin vent and allow any trapped air to escape Collect any water that escapes so that it do...

Страница 29: ...l properly If a pump change is required for any reason valve off the boiler and drain approximately 1 or 2 gallons approx 4 8L of water from it Turn off the main disconnect switch and unplug the pump...

Страница 30: ...acing shut off the 120 volt power Unplug the transformer wires from the transformer unscrew the two fixing screws and remove the transformer Fit the replacement transformer in reverse order 8 8 PWM Bo...

Страница 31: ...om gas valve flange Unplug the blower and the ignitor Remove the bolts from the blower and pull the blower out The boiler assembly may now be removed from the jacket After removal of the boiler assemb...

Страница 32: ...WIRING 24V 115V G Y GREEN WITH YELLOW V VIOLET GR GRAY G GREEN O ORANGE BR BROWN BL BLUE Y YELLOW R RED W WHITE BK BLACK COLOUR LEGEND FACTORY WIRING BL W BL W G LINE CONN GND MV1 W S2 FS L2 L1 S1 120...

Страница 33: ...durance in setpoint mode instead of outdoor reset mode The ignition control uses LED indication to display the following fault codes Steady On Internal control failure 2 Flashes Erroneous flame signal...

Страница 34: ...o disconnect anything to measure the flame current signal To measure the flame signal connect an analog DC microammeter to the FC terminals on the ignition control per Figure 37 The meter should read...

Страница 35: ...range adjust the gas valve calibration Always adjust the air orifice first To adjust the gas valve calibration see figure 35 for the location of the offset pressure port and the offset adjustment Whe...

Страница 36: ...ct install a smaller gas orifice so that the O2 will rise above 4 or the CO2 will drop to 8 natural or 9 LP The CO2 O2 readings may be influenced by cross contamination Suspect cross contamination if...

Страница 37: ...ons of minerals in the water These minerals may cause fouling of the DHW heat exchanger over an extended period of time lime build up Other minerals which react more quickly in well systems mostly mag...

Страница 38: ...Repair Kit 2400 538 2400 538 16 Anti Condensing Valve Operator Only 2400 539 2400 539 17 Water Flow Switch 2400 542 2400 542 18 Safety Limit 230 F 2400 550 2400 550 2400 550 2400 550 2400 550 2400 55...

Страница 39: ...Endurance Page 39...

Страница 40: ...x 800 559 1583 Customer Service Service Advisors 20 Industrial Way Rochester NH 03867 603 335 6300 Fax 603 335 3355 1869 Sismet Road Mississauga Ontario Canada L4W 1W8 905 238 0100 Fax 905 366 0130 ww...

Отзывы: