Premier Ductable Heaters
Owner’s Manual • Premier 350
29
2. Securely connect pressure gauges at these points.
3. Open the fuel supply valves to the heater and recon-
nect the heater electrical supply.
4. Start the heater
FIG. 38
OUTLET PRESSURE TAP
INLET PRESSURE TYPE
INTERNAL PRESSURE REGULATOR
GAUGE AT VALVE INLET
GAUGE AT VALVE OUTLET
FIG. 39
OUTLET
GAUGE
INLET
GAUGE
GAS CONTROL
LOW HEAT
HIGH HEAT
OFF
ON
LO
HI
0
5
10
15 20 25
30
35
0
5
10
15 20 25
30
35
C. Reading Pressures
1. With the heater operating, the pressure gauges should
read the pressures speci
fi
ed on the dataplate.
2. Do the readings at the inlet and outlet pressure gauges
agree with that speci
fi
ed on the dataplate? If so, then
no further checking or adjustment is required. Proceed
to section D.
3. If the inlet pressures do not agree with that speci
fi
ed
on the dataplate, then the regulator controlling gas
pressure to the heater requires adjustment.
4. If the inlet pressure is correct but the burner manifold
pressure does not agree with that speci
fi
ed on the
dataplate, then the gas control valve’s internal pressure
regulator needs adjustment:
Premier 350DF Heater:
-- Remove the regulator cap on the control valve.
-- Using a standard screwdriver turn the adjusting
screw clockwise (to increase pressure) or counter-
clockwise
(to decrease pressure) until the burner manifold
pressure is set.
-- Install regulator cap.
-- Proceed to COMPLETION.
Premier 350 Propane Gas Heater
-- Turn the thermostat down to its lowest setting.
-- Remove the cap from the high and low heat adjust-
ing screws at the two stage pressure regulator on
the gas control valve.
-- Slowly turn up the thermostat until a pressure is read
no greater than 2.0 in.W.C./.49 kPa at the outlet
pressure gauge.
-- If less than these pressures is observed, the low
heat setting at the regulator on the gas control will
require adjusting.
-- Turn clockwise to increase, or counterclockwise to
decrease pressure.
-- Turn the thermostat completely up.
-- You should see the gas pressure increase from 2.0
in. W.C./ .49 kPa at low heat to 8.0 in.W.C./2.0 kPa
high heat.
-- If less or greater than these pressure are observed
the high heat setting must be adjusted clockwise or
counterclockwise accordingly until proper pressure
is achieved.
D. Completion
1. Once the proper inlet and burner manifold pressures
have been con
fi
rmed and/or properly set, close the
fuel supply valve to the heater and allow the heater
to burn off any gas remaining in the gas supply line.
2. Disconnect the heater from its electrical supply and
close fuel supply valve.
3. Remove the gauges.
4. Install pressure tap plugs.
5. Open fuel supply valve and reconnect electrical
supply to heater. Start the heater and check for gas
leaks.
6. Set thermostat to desired temperature.
SINGLE STAGE
TWO STAGE
Содержание Premier 350
Страница 40: ...Premier Ductable Heaters www lbwhite com Owner s Manual Premier 350 40 Service Parts Identification Schematic...
Страница 43: ...Premier Ductable Heaters Owner s Manual Premier 350 43 Notes...
Страница 87: ...Calefactores canalizados Premier Manual del usuario Premier 350 43 Notas...
Страница 131: ...Appareils de chauffage canalisables Premier Guide du propri taire Premier 350 43 Remarques...